Table 9- 46
Response identifier
0
1
2
3
4
5
6
7
1) The required element of the parameter description is specified in IND (second word).
2) The required element of the indexed parameter is specified in IND (second word).
If the response identifier is 7 (request cannot be processed), one of the error numbers listed
in the following table will be saved in parameter value 2 (PWE2).
Table 9- 47
No.
0
1
2
3
4
5
6
7
11
12
17
101
102
104
106
200/201
204
Function Manual
Function Manual, 01/2011, 6SL3097-4AB10-0BP3
Response identifier (inverter → master)
Description
No response
Transfer parameter value (word)
Transfer parameter value (double word)
Transfer descriptive element
Transfer parameter value (field, word)
Transfer parameter value (field, double word)
Transfer number of field elements
Request cannot be processed, task cannot be performed (with error number)
Error numbers for the response "Request cannot be processed"
Description
Impermissible parameter number (PNU)
Parameter value cannot be changed
Minimum/maximum not achieved or exceeded
Wrong subindex
No field
Wrong parameter type / wrong data type
Setting is not permitted (only resetting)
The descriptive element cannot be changed
Not in "master control" mode
Keyword missing
Request cannot be processed on account of the
operating state
Parameter number is currently deactivated
Channel width is insufficient
Illegal parameter value
Request not included / task is not supported
Changed minimum/maximum not achieved or
exceeded
The available access authorization does not
cover parameter changes
9.5 Communication using USS
1)
2)
2)
Remarks
Parameter does not exist
The parameter can only be read
An individual parameter was
addressed with a field request and
subindex > 0
Confusion of word and double word
Index is outside the parameter field[]
Description cannot be changed
Change request without "master
control" mode (see p0927)
The current inverter status is not
compatible with the received request
Dependent on the operating mode of
the inverter
Communication channel is too small
for response
The parameter can only assume
certain values
After request identifier
5,11,12,13,14,15
The maximum or minimum can be
limited further during operation
Communication
647