Communication
9.2 Communication according to PROFIdrive
Bit
Meaning
10
Master control by PLC
Note:
This bit should not be set to "1" until the PROFIdrive has returned an appropriate status via ZSW1.9 = "1".
11
Start referencing
12
Reserved
13
External block change
14
Reserved
15
Reserved
STW2 (control word 2)
See function diagram [2444]
Table 9- 7
Description of STW2 (control word 2)
Bit
Meaning
0
Drive data set selection DDS bit 0
1...6
Reserved
7
Parking axis
8
Travel to fixed stop
(not with telegrams 9, 110)
9..10 Reserved
11
Motor changeover
12
Master sign-of-life bit 0
13
Master sign-of-life bit 1
14
Master sign-of-life bit 2
15
Master sign-of-life bit 3
536
Remarks
1
Control by PLC
This signal must be set so that the process data
transferred via PROFIdrive are accepted and
become effective.
0
No control by PLC
Process data transferred via PROFIdrive are
rejected - i.e. assumed to be zero.
1
Start referencing
0
Stop referencing
-
-
0/1
External set change is initiated
0
No effect
-
-
-
-
Remarks
-
Drive data set selection
(5 bit counter)
-
-
1
Request parking axis (handshake with ZSW2 bit
7)
0
No request
1
Select "Travel to fixed stop"
The signal must be set before the fixed stop is
reached.
1/0
Deselect "Travel to fixed stop"
The signal must be set before the fixed stop is
reached
-
-
0/1
Motor changeover complete
0
No effect
-
User data integrity (4-bit counter)
-
-
-
Function Manual, 01/2011, 6SL3097-4AB10-0BP3
Parameter
BI: p0854
BI: p2595
-
BI: 2632
-
-
Parameter
BI: p0820[0]
-
BI: p0897
BI: p1545
-
BI: p0828[0]
CI: p2045
Function Manual