Which signal can be output via measuring sockets?
The signal to be output via a measuring socket is specified by parameterizing the connector
input p0771[0...1].
Important measuring signals (examples):
r0060
r0063
r0069[0...2]
r0075
r0076
r0077
r0078
Scaling
Scaling specifies how the measuring signal is processed. A straight line with 2 points must
be defined for this purpose.
Example:
x1 / y1 = 0.0% / 2.49 V x2 / y2 = 100.0% / 4.98 V (default setting)
– 0.0% is mapped onto 2.49 V
– 100.0% is mapped onto 0.00 V
Offset
The offset is applied additively to the signal to be output. The signal to be output can thus be
displayed within the measuring range.
Limitation
● Limitation On
● Limitation off
Function Manual
Function Manual, 01/2011, 6SL3097-4AB10-0BP3
CO: Speed setpoint before speed setpoint filter
CO: Actual speed value
CO: Phase currents actual value
CO: Field-generating current setpoint
CO: Field-generating actual current
CO: Torque-generating current setpoint
CO: Torque-generating actual current
If signals are output outside the permissible measuring range, the signal is limited to 4.98
V or to 0V.
The output of signals outside the permissible measuring range causes a signal overflow.
In the event of an overflow, the signal jumps from 0 V to 4.98 V or from 4.98 to 0 V.
Diagnostics
5.2 Diagnostics via STARTER
103