CU_ZSW1 (status word of the DO1 telegram (telegrams 39x))
See function diagram [2496].
Table 9- 30
Description of CU_ZSW1 (status word of the CU)
Bit
Meaning
0...3 Reserved
3
Fault active
4...5 Reserved
6
Reserved
7
Alarm active
8
Synchronization (SYNC)
9
Alarm pending
10
Fault pending
11
Safety signal pending
12
Slave sign-of-life bit 0
13
Slave sign-of-life bit 1
14
Slave sign-of-life bit 2
15
Slave sign-of-life bit 3
Function Manual
Function Manual, 01/2011, 6SL3097-4AB10-0BP3
Remarks
1
Fault active.
The active faults are stored in the fault buffer.
0
No fault active.
There is no active fault in the fault buffer.
0
1
Alarm active.
The active alarms are stored in the alarm buffer.
0
No alarm active.
No active alarm is present in the alarm buffer.
1
No group bit for module line-up alarm.
0
Group bit for alarm is active, ORed across all DOs
including the CU of the module line-up.
1
No group bit for module line-up fault.
0
Group bit for fault is active, ORed across all DOs
including the CU of the module line-up, plus
propagations.
1
No safety signal pending
0
Safety signal pending
1-15
Cyclic advance
Initialization, no sign of life available
0
1-15
0
1-15
0
1-15
0
9.2 Communication according to PROFIdrive
Communication
Parameter
BO: r2139.3
BO: 2139.7
BO: r3114.9
BO: r3114.10
BO: r3114.11
Implicitly
interconnected
571