3. Programming

Control Modules

A typical control module autoprogram screen is shown below:
Control modules default to Zone 00 (general alarm). All Type Code options are silenceable except
Relay and Strobes. The selection of control module Type Codes may change their function. Select the
Type Code from the library list shown below, using the arrow keys as described in "New Detectors" on
page 45.
Select an adjective descriptor from the library list shown in Table 3 on page 45. Use the arrow keys as
described in the New Detectors section. Control modules may be assigned to a maximum of three
software zones (refer to "Appendix C: Software Zones" on page 80). Zone Z00 represents general
alarm. All control modules are assigned to Zone Z00 upon initial power-up.

Point Edit

While displaying the Program Level 1 Menu screen (see "Program Change – Level One" on page 44),
pressing the 2 key allows for editing of the point (addressable device) descriptor screens. These screens
show the device type, the device address, adjective and noun field descriptors and the software zone
locations that the point is assigned to. Point editing is performed after autoprogramming and may be
done at any time, except during an alarm condition. The following display will appear:
For example, select detector address 3 program edit by pressing * key (* = detector), followed by
numeric key 3, followed by the
(# = module), press the 3 key, then press the
control panel displays the next higher address where a device is installed. After finished editing, press
the
user may press the up or down arrow key to display the next lower or higher existing point.
Using software PN #AFP100V1.0 or greater, to edit NAC 1 or NAC 2, press the * key, then the # key,
the press 1 for NAC 1 or 2 for NAC 2. Select either 'BELL_CKT' for silenceable functionality or
'STROBE' for nonsilenceable functionality. Use the system edit menu described in "System Edit" on
page 49, to select coding. Coding is only possible if the NAC is programmed as 'BELL_CKT'. The
point display formats and the method of editing are described in "Autoprogram" on page 44.
48
Technical Manuals Online! - http://www.tech-man.com
PROGRM CONTROL
<ADJ>
Type Code Label
CONTROL
BELL CKT
HORN CKT
SOUNDERS
_________
RELAY
STROBES
Table 6 Control Module Type Codes
POINT PROG.
PRESS */#, AA,ENTER
key, the display returns to the above menu. Rather than reentering the next point number, the
ENTER
ZNN ZNN ZNN
Special Function
none (default)
silenceable
silenceable
silenceable
none (blank label for use when no other
Type Code applies), silenceable
ignore open circuit (
nonsilenceable
key. To select module address 3 for program edit, press the # key
ENTER
key. If there is no device installed at this address, the
ENTER
Program Change – Level One
CNN
nonsilenceable)
EDIT
AFP-100/AFP-100E Instruction PN 51010:C1 02/06/2002