Occupancy Sensor Setup

Configuring Occupancy Sensor Settings (optional)

Occupancy Sensor Settings
Main menu
Note: These settings affect all sensors assigned to the
Zone Setup
Sensor Setup
Grace Period: If the GRAFIK Eye QS control unit is transitioning
to an unoccupied state, motion detected within the grace
period will return the lights to the previously occupied level.
Sensor Setup
Range: 15 – 30 seconds (default 15 seconds).
Vacancy Delay: An additional time delay after vacancy is
Daylight
detected and before unoccupied action occurs. Use when
Occupancy
occupancy sensor does not provide sufficient delay.
Range: 0 – 30 minutes (default 0 minutes).
Auto Turnoff: If lights assigned to an occupancy sensor are
Occ Sensor
turned on manually without the sensor reporting occupancy,
the GRAFIK Eye QS control unit can be set to automatically
Settings
turn off the lights after a set time delay. Disable this feature by
setting the time delay to 0 (disabled).
Diagnostics
Range: Disabled or 1 – 30 minutes (default Disabled).
Zone Fade: When in Zone Mode, lights can be set to fade to
Settings
the unoccupied levels over this period of time.
Range: 0 – 59 seconds; 1 – 10 minutes (default 10 seconds).
Auto Turnoff
Configuring the Sensor Settings:
Zone Fade
1. Enter programming mode.
2. Use the Master buttons to highlight "Sensor Setup" and press
the OK button to accept.
Auto Turnoff
3. Use the Master buttons to highlight "Occupancy" and press
the OK button to accept.
5 minutes
4. Use the Master buttons to highlight "Settings" and press the
OK button to accept.
5. Use the Master buttons to highlight the setting you wish to
configure. Press the OK button to accept.
6. Use the Master buttons to adjust the value of the selected
Saved
Saved
setting. Press the OK button to accept.
7. The info screen will confirm that your setting has been saved.
8. Exit programming mode.
®
1
9
GRAFIK Eye QS control unit.
For additional information, see the complete installation and operation guide at www.lutron.com/qs
GRAFIK Eye QS with EcoSystem Control Unit Quick Installation and Operation Guide 20