Configuring Occupancy Sensor Settings; (Optional) - Lutron Electronics GRAFIK Eye QSGRN-6PCE Installation And Operation Manual

Table of Contents

Advertisement

Occupancy Sensor Setup
Configuring Occupancy Sensor Settings (optional)
Occupancy Sensor Settings
Main menu
Note: These settings affect all sensors assigned to the
Zone Setup
Sensor Setup
Grace Period: If the GRAFIK Eye
transitioning to an unoccupied state, motion detected within
the grace period will return the lights to the previously
Sensor Setup
occupied level.
Range: 15 – 30 seconds (default 15 seconds).
Daylight
Vacancy Delay: An additional time delay after vacancy is
Occupancy
detected and before unoccupied action occurs. Use when
occupancy sensor does not provide sufficient delay.
Range: 0 – 30 minutes (default 0 minutes).
Occ Sensor
Auto Turnoff: If lights assigned to an occupancy sensor are
turned on manually without the sensor reporting occupancy,
Settings
the GRAFIK Eye
turn off the lights after a set time delay. Disable this feature by
Diagnostics
setting the time delay to 0 (disabled).
Range: Disabled or 1 – 30 minutes (default Disabled).
Settings
Zone Fade: When in Zone Mode, lights can be set to fade to
the unoccupied levels over this period of time.
Auto Turnoff
Range: 0 – 59 seconds; 1 – 10 minutes (default 10 seconds).
Zone Fade
Configuring the Sensor Settings:
1. Enter programming mode.
2. Use the Master buttons to highlight "Sensor Setup" and press
Auto Turnoff
the OK button to accept.
3. Use the Master buttons to highlight "Occupancy" and press
5 minutes
the OK button to accept.
4. Use the Master buttons to highlight "Settings" and press the
OK button to accept.
5. Use the Master buttons to highlight the setting you wish to
configure. Press the OK button to accept.
Saved
Saved
6. Use the Master buttons to adjust the value of the selected
setting. Press the OK button to accept.
7. The info screen will confirm that your setting has been saved.
8. Exit programming mode.
®
GRAFIK Eye
QS control unit.
®
QS control unit can be set to automatically
®
QS control unit is
®
GRAFIK Eye
QS Control Unit Installation and Operation Guide 32
®
Master
buttons
OK
OK
button
Timeclock
(back) button