Arming / disarming with entry / exit delay

Arming inside the secured area, e.g. with touch keypad
1.
2.
3.
4.
5.
Programming entry / exit route
1.
2.
Exit point type
Initial follower
Follower
Exit
Bosch Security Systems B.V.
Select the area in the properties field of the Key Switch > Area.
In the properties field of the Touch Keypad, include the area in the scope Local Area or
Additional Areas in Scope
Connect one free output in each case with the device LED.
Using the wizard, program one output with the behavior item Area Armed and a second
output with the behavior item Area Disarmed.
The signal must be time-limited. Enter a corresponding time (typically 10 seconds /
maximum 30 seconds) for Activation Duration.
Connect a free output with the device LED.
Variant A: Blocking element is actively controlled CLOSED. Using the wizard, program
an output with the behavior item Area Armed
or
Variant B: Blocking element is actively controlled OPEN. Using the wizard, program an
output with the behavior item Area Disarmed.
The signal must be static; enter 00:00:00 for Activation Duration.
Refer to the manufacturer's connection instructions for further information.
Include a new area if not yet present.
Include a touch keypad if not yet present.
Include the area in the scope of the touch keypad: Local Area.
Program touch keypad for arming with exit delay: Use Area Normal Delay Time.
The value for the entry / exit delay can be adapted if required: Area Manager > Area >
Timing and Delays:
normal entry delay (typically 45 sec. / at least 30 sec.)
normal exit delay (typically 60 sec.)
Program all points of the entry / exit route to the point type intrusion.
Select the type of exit point optionally for exit route points:
Behavior
1
Point without prevention of arming readiness, e.g. PIR that has the
touch keypad in the detection area. Important: point must be in
normal state after exit, otherwise an alarm will be tripped
1
Point that does not trip an alarm as long as the exit delay is
running. Only relevant for option MAP5000 Panel > Armed State
At Exit Delay Start
Door point that must be mandatorily tripped once upon leaving
the area. The option MAP5000 Panel > Unvacated Premises must
be activated