Modular Alarm Platform 5000
Bosch Data Bus cable routing
4.1.1
Internal / external Bosch Data Bus
The MAP5000 system contains two Bosch Data Buses (BDB), which are used to connect the
system modules to the MAP5000 panel.
Internal BDB
The maximum length of the internal BDB is 3 m.
It is used for connecting the MAP5000 panel and other modules in the MAP panel enclosure
(Internal BDB connections, page 46).
External BDB
The maximum length of the external BDB is 1000 m from the MAP5000 panel.
It is used for connecting system modules in remote operation.
Requirements for BDB wiring
There are no special requirements concerning the following:
–
–
–
The minimum wire diameter is determined on the basis of the required cable length:
–
–
–
Modules on the BDB
System module
ICP-MAP0007-2 MAP DE interface module
ICP-MAP0010 MAP LSN gateway
Bosch Security Systems B.V.
Solid or stranded
Twisted or untwisted
Shielded or unshielded
0.6 mm up to 450 m
0.8 mm up to 750 m
1.0 mm up to 1000 m
Internal BDB
X
X
Installation manual
Connections | en
External BDB
1
X
2024-10 | V26 | F.01U.168.332