VACON® NXP IP00 Drive Modules
Operating Guide
Specifications
Troubleshooting
Change the control unit.
12.12.82 Fault 37 - Device changed (same type), Subcode S1 - Control board
Cause
A new option board has replaced the old one in the same slot. The parameters are available in the drive.
Troubleshooting
Reset the fault. The device is ready for use. The drive starts to use the old parameter settings.
12.12.83 Fault 38 - Device added (same type), Subcode S1 - Control board
Cause
The option board was added. The same option board has been used in the same slot before. The parameters are available in the
drive.
Troubleshooting
Reset the fault. The device is ready for use. The drive starts to use the old parameter settings.
12.12.84 Fault 39 - Device removed
Cause
An option board was removed from the slot.
Troubleshooting
The device is not available. Reset the fault.
12.12.85 Fault 40 - Device unknown, Subcode S1 - Unknown device
Cause
An unknown or mismatching device was connected (the power unit or option board).
Troubleshooting
Ask instructions from the local distributor.
12.12.86 Fault 40 - Device unknown, Subcode S2 - StarCoupler: power sub units are not identical
Cause
An unknown or mismatching device was connected (the power unit or option board).
Troubleshooting
Ask instructions from the local distributor.
12.12.87 Fault 40 - Device unknown, Subcode S3 - StarCoupler is not compatible with the control
board
Cause
An unknown or mismatching device was connected (the power unit or option board).
Troubleshooting
Ask instructions from the local distributor.
12.12.88 Fault 40 - Device unknown, Subcode S4 - Wrong PropertiesType in control board EEPROM
Cause
An unknown or mismatching device was connected (the power unit or option board).
Troubleshooting
Ask instructions from the local distributor.
12.12.89 Fault 40 - Device unknown, Subcode S5 - Wrong VACON® NXP control board EEPROM size
detected
Cause
An unknown or mismatching device was connected (the power unit or option board).
Troubleshooting
Ask instructions from the local distributor.
Danfoss A/S © 2023.09
AQ351737303996en-000201 / DPD00888 | 165