VACON® NXP IP00 Drive Modules
Operating Guide
Troubleshooting
Do a check of the encoder board.
Do a check of the terminals.
Do a check of the board connections.
12.12.107 Fault 43 - Encoder fault, Subcode S6 - Serial communication fault
Cause
Problem detected in encoder signals.
Serial communication fault. The encoder cable is not connected or there are interferences in the cable.
Troubleshooting
Check cabling between encoder and OPTBE, especially Data and Clock signals.
Check that actual encoder type matches with OPTBE "Operating mode" parameter.
12.12.108 Fault 43 - Encoder fault, Subcode S7 - Ch A / Ch B Mismatch
Cause
Problem detected in encoder signals.
Encoder channels A and B are mismatched.
Troubleshooting
Do a check of the cable connections and terminals.
12.12.109 Fault 43 - Encoder fault, Subcode S8 - Resolver/Motor pole pair mismatch
Cause
Problem detected in parameterization of option board.
There is a mismatch of the resolver/ motor pole pair number. Resolver pole pair number (if >1) is not matching the motor pole pair
number.
Troubleshooting
Check that OPTBC parameter "Resolver Poles" and possible Gear Ratio parameters in application match motor pole count.
12.12.110 Fault 43 - Encoder fault, Subcode S9 - Missed Start Angle
Cause
Encoder zero positioning identification run has not been made.
The encoder start angle is missing.
Troubleshooting
Make encoder identification run.
12.12.111 Fault 43 - Encoder fault, Subcode S10 - Sin/Cos encoder feedback is missing
Cause
Problem detected in encoder signals.
For the closed loop control, encoder modes "EnDat only" or "SSI only" (absolute channel only) are not allowed.
Troubleshooting
Do a check of the wiring, jumper settings, and encoder mode.
Change OPTBE "Operating mode" parameter is either "EnDat+SinCos", "SSI+SinCos" or "SinCos only", or avoid using closed loop
control.
12.12.112 Fault 43 - Encoder fault, Subcode S11 - Encoder angle is drifting
Cause
Error angle between the angle read from the absolute channel and the angle calculated from the incremental channels.
Troubleshooting
Check the encoder cable, cable shield, and grounding of the cable shield.
Check the mechanical mounting of the encoder and make sure that the encoder is not slipping.
Check the encoder parameters (for example, encoder ppr).
Danfoss A/S © 2023.09
Specifications
AQ351737303996en-000201 / DPD00888 | 169