VACON® NXP IP00 Drive Modules
Operating Guide
12.12.55 Fault 16 - Motor overtemperature
Cause
There is too heavy a load on the motor.
It is possible to set different responses in the application for this fault. See parameter group Protections.
Troubleshooting
Decrease the motor load.
If there is no motor overload, do a check of the temperature model parameters.
12.12.56 Fault 17 - Motor underload
Cause
Motor underload protection has tripped.
It is possible to set different responses in the application for this fault. See parameter group Protections.
Troubleshooting
Check the load.
Check underload protection parameterization.
12.12.57 Fault 18 - Unbalance, Subcode S1 - Current unbalance
Cause
Unbalance between power modules in paralleled power units.
This fault is type A fault (Alarm).
Troubleshooting
If the fault occurs again, ask instructions from the local distributor.
12.12.58 Fault 18 - Unbalance, Subcode S2 - DC voltage unbalance
Cause
Unbalance between power modules in paralleled power units.
This fault is type A fault (Alarm).
Troubleshooting
If the fault occurs again, ask instructions from the local distributor.
12.12.59 Fault 19 - Current overload
Cause
Motor current overload warning.
Troubleshooting
Ask instructions from the local distributor.
12.12.60 Fault 22 - Parameter fault, Subcode S1 - Firmware interface power down variable check-
sum error
Cause
Parameter save fault.
Operation malfunction
defective component
Troubleshooting
If the fault occurs again, ask instructions from the local distributor.
12.12.61 Fault 22 - Parameter fault, Subcode S2 - Firmware interface variable check sum error
Cause
Parameter save fault.
Operation malfunction
defective component
Troubleshooting
If the fault occurs again, ask instructions from the local distributor.
Danfoss A/S © 2023.09
Specifications
AQ351737303996en-000201 / DPD00888 | 161