Fuse Sizes For 525-690 V Ac, 6-Pulse - Danfoss VACON NXP IP00 Operating Manual

Drive modules
Table of Contents

Advertisement

VACON® NXP IP00 Drive Modules
Operating Guide
12.4.7 Fuse Sizes for 525–690 V AC, 6-pulse
The aR fuses are thermally rated into switch fuse in 50 °C (122 °C) ambient temperature.
Table 51: Fuse Sizes for 525–690 V AC, FR8–FR9, 6-pulse
Enclosure size
FR8
FR9
Table 52: Fuse Sizes (Bussmann) for 525–690 V AC, FR10–FR12, 6-pulse
Enclo-
Drive
DIN 43620
sure size
type
aR fuse part
nr.
FR10
261
170M5813
325
170M5813
385
170M5813
416
170M5813
FR11
460
170M8547
502
170M8547
590
170M5813
FR12
650
170M5813
750
170M5813
820
170M5813
FR12
170M6202
(2)
DC-link
SHT fuses can be assembled into same size DIN fuse base
1
In FR12 (12-pulse drive) or in FR12 (6- or 12-pulse) with internal brake, the DC-links between units are connected together. If connected together,
2
there must be DC-link fuses in DC-minus and DC-plus poles between the units. (In 6-pulse drive without internal brake, DC-links between units are
separate and there is no need for fuses.)
138 | Danfoss A/S © 2023.09
Drive type
Fuse (gG/gL) [A]
0062
80
0080
80
0100
100
0125
160
0144
160
0170
200
0208
250
DIN 43653 (110 mm)
Fuse size
aR fuse part
nr.
DIN 2
170M5213
DIN 2
170M5213
DIN 2
170M5213
DIN 2
170M5213
3SHT
170M6216
(1)
3SHT
170M6212
(1)
DIN 2
170M5213
DIN 2
170M5213
DIN 2
170M5213
DIN 2
170M5213
3SHT
170M5986
(1)
Fuse Class Fast Acting (T/J) [A]
80
100
125
200
200
250
300
Flush end contacts (met-
ric)
Fuse size
aR fuse part
nr.
2TN/110
170M5463
2TN/110
170M5463
2TN/110
170M5463
2TN/110
170M5463
3TN/110
170M6466
3TN/110
170M6466
2TN/110
170M5463
2TN/110
170M5463
2TN/110
170M5463
2TN/110
170M5463
2TN/110
170M8604
AQ351737303996en-000201 / DPD00888
Specifications
Fuse In
Fuses
[A]
per
drive
Fuse size
2BKN/50
700
3
2BKN/50
700
3
2BKN/50
700
3
2BKN/50
700
3
3BKN/50
1250
3
3BKN/50
1250
3
2BKN/50
700
6
2BKN/50
700
6
2BKN/50
700
6
2BKN/50
700
6
3BKN/75
500
2

Advertisement