Operating Guide
12.12.31 Fault 8 - System fault, Subcode S41 - OPTAF: STO channels are not active when the ther-
mistor trip is active
Cause
Single hardware problem detected in the thermistor input.
Troubleshooting
Change the OPTAF board.
12.12.32 Fault 8 - System fault, Subcode S42 - OPTAF: Test pulse low is not detected on thermistor
Cause
Single hardware problem detected in the thermistor input.
Troubleshooting
Change the OPTAF board.
12.12.33 Fault 8 - System fault, Subcode S43 - OPTAF: Test pulse high is not detected on thermistor
Cause
Single hardware problem detected in the thermistor input.
Troubleshooting
Change the OPTAF board.
12.12.34 Fault 8 - System fault, Subcode S44 - OPTAF: STO channel 1 is not active, even if the ana-
log input supervision indicates
Cause
Single hardware problem detected in Safe Disable inputs or in the thermistor input.
Troubleshooting
Change the OPTAF board.
Change the control board.
12.12.35 Fault 8 - System fault, Subcode S45 - OPTAF: STO channel 2 is not active, even if the ana-
log input supervision indicates
Cause
Single hardware problem detected in Safe Disable inputs or in the thermistor input.
Troubleshooting
Change the OPTAF board.
Change the control board.
12.12.36 Fault 8 - System fault, Subcode S46 - OPTAF: Thermistor or analog input is not set, even if
STO is active
Cause
Single hardware problem detected in Safe Disable inputs or in the thermistor input.
Troubleshooting
Change the OPTAF board.
Change the control board.
12.12.37 Fault 8 - System fault, Subcode S47 - OPTAF: Board mounted in old NXP control board
with no safety hardware
Cause
OPTAF board mounted in old VACON
Troubleshooting
Change the control board to VB00561 revision H or newer.
12.12.38 Fault 8 - System fault, Subcode S48 - OPTAF: Mismatch between Therm Trip (HW) parame-
ter and jumper setting
Cause
The parameter Expander boards/ SlotB/ Therm Trip(HW) is set to OFF even though the jumper X12 is not cut.
Danfoss A/S © 2023.09
NXP control board, which is not equipped with the Safe Disable function.
®