12.12.141 Fault 86 - Condition-based Monitoring, Subcode A5 - Motor Stator Winding Current
Warning S1
Cause
Current unbalance has exceeded the detection high limit.
Troubleshooting
Check motor stator windings.
12.12.142 Fault 86 - Condition-based Monitoring, Subcode A6 - Motor Stator Winding Voltage
Warning S1
Cause
Voltage unbalance has exceeded the detection high limit.
Troubleshooting
Check motor stator windings.
12.12.143 Fault 86 - Condition-based Monitoring, Subcode A7 - Vibration Fault
Cause
Vibration has exceeded the detection high limit.
Troubleshooting
Check root cause for increased vibration.
12.12.144 Fault 86 - Condition-based Monitoring, Subcode A8 - Vibration Warning S2
Cause
Vibration has exceeded the detection high limit.
Troubleshooting
Check root cause for increased vibration.
12.12.145 Fault 86 - Condition-based Monitoring, Subcode A9 - Vibration Warning S1
Cause
Vibration has exceeded the detection high limit.
Troubleshooting
Check root cause for increased vibration.
12.12.146 Fault 86 - Condition-based Monitoring, Subcode A10 - Load Fault
Cause
Load outside of the window limits.
Troubleshooting
Check root cause for excessive overload or underload.
12.12.147 Fault 86 - Condition-based Monitoring, Subcode A11 - Load Warning S2
Cause
Load outside of the window limits.
Troubleshooting
Check root cause for excessive overload or underload.
12.12.148 Fault 86 - Condition-based Monitoring, Subcode A12 - Load Warning S1
Cause
Load outside of the window limits.
Troubleshooting
Check root cause for excessive overload or underload.