Operating Procedure - M-system 47DAC Operating Manual

Ac input digital panel meter
Table of Contents

Advertisement

9.1.1 OPERATING PROCEDURE

1,3
1
Hold down Alarm/↓ button for 3 seconds or more to move on
to Alarm Setting Mode.
• The alarm output pattern is indicated.
• The SD indicates ' A LM PTN' .
NOTE
With the bank switching set to "enabled via the front button control" , the bank No. is indicated (' A LM BNK' on the SD).
Press Alarm/↓ button to go to the alarm output pattern setting.
2
Press Shift and Up buttons to select the alarm output pattern.
• Select 'NORMAL' or 'ZONE' .
3
Press Alarm/↓ or Scale/↑ button to apply the new setting.
• And the next parameter setting is indicated.
NOTE
• Press Alarm/↓ button, and the LL alarm setpoint will be indicated (' A LARMLL' on the SD).
• Press Scale/↑ button, and the main display blinking at alarm will be indicated (' A LMBLNK' on the SD), or the bank No.
will be indicated (' A LM BNK' on the SD) with the bank switching set to "enabled via the front button control" .
4
■ TO SET THE NEXT PARAMETER,
Skip to Step 2 in "9.2 ALARM SETPOINT" .
■ TO QUIT,
Hold down Alarm/↓ or Scale/↑ button for 1 second or more to return to Measuring Mode.
2
3
2
NOTE
The following figures are display examples. The displays
depend on the settings.
47DAC OPERATING MANUAL EM-9518-B Rev.4
Blinking
97

Advertisement