Appendix IV:The configuration setting of M-7000/DL module
PMC/PMD allows connection to ICP DAS M-7000/DL modules for the I/O channel
data settings and data retrieve. However, for other configuration of the M-7000/DL
modules must be completed via DCON Utility in advance, so that the PMC/PMD can
accurately connect to M-7000/DL module. The procedures for M-7000/DL module
parameter settings are as follow:
1. Connect the M-7000/DL modules to the PC (with DCON Utility installed) via
RS-485 cable, make sure the RS-485 cable is properly connected. For PC to
receive RS-485 signals, a RS-232 to RS-485 or a USB to RS-485 converter is
required. For more converter information, please refer to ICP DAS converter
product page:
http://www.icpdas.com/root/product/solutions/industrial_communication/converte
r/converter_selection.html
2. If the ICP DAS I/O module is M-7000 series, please follow the steps as
below for the configuration setting.
A. You can download DCON Utility from the link below, and Install the
DCON Utility on PC
http://ftp.icpdas.com/pub/cd/8000cd/napdos/driver/dcon_utility/