11.2.15 Internal Register; Figure11-48 : Internal Register Action Setting Page - ICP DAS USA PMC-523 Series User Manual

Power meter concentrator
Table of Contents

Advertisement

ICP DAS PMC-523x/PMC-224x/PMD Series User Manual
list of the "Rule" field.
ii Specify the Rule status to be Disable or Enable from the dropdown
list of the "Action" field. When the Action being executed, the Rule
status will be changed to specified status.
iii Click "OK" button to confirm the settings and return to the Rule
settings page.

11.2.15 Internal Register

You can modify the value of Internal Register in the THEN/ELSE
Action statement; the editing page for Internal Register Action Setting
is shown as below:
Follow the steps below:
i Select the pre-defined Internal Register from the dropdown list of
the "No" field.
enabled in Advanced Setting.
ii Specify the Operator in the "Operator" field. The 5 operators are as
follow:
 "=":Indicate assign the new Internal Register value as the
 "+=":Indicate assign the new Internal Register value as the
 "-=":Indicate assign the new Internal Register value as the
 "*=":Indicate assign the new Internal Register value as the
 "/=":Indicate assign the new Internal Register value as the

Figure11-48 : Internal Register action setting page

Please note: the Internal Register you select has to be
value in "Value" field.
original Internal Register value plus the value in "Value" field.
original Internal Register value minus the value in "Value"
field.
original Internal Register value times the value in "Value" field.
original Internal Register value divided by the value in "Value"
field.
230