Page 1
ICP DAS PMC-523x/PMC-224x/PMD (Power Meter Concentrator) Series User Manual [Version 3.6.6]...
Page 2
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual Disclaimer The information furnished by ICP DAS Co. Ltd. (hereinafter “ICP DAS”) is accurate and reliable to ICP DAS’s best knowledge. ICP DAS reserves the right to change the content of this manual at any time without notice.
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual Table of Contents System Introduction ..................1 Before Installation ..................6 System Login ....................7 System Main Page ..................8 System function area ................. 9 Rules management toolbar ............9 4.1.1 Real-time information area............ 12 4.1.2...
Page 4
Modbus RTU Power Meter Setting ........88 7.1.5 7.1.6 Modbus TCP Power Meter Setting ......... 91 XV-Board Setting (PMD series does not support this function.) ... 94 7.2.1 XV-Board DI Channel Settings ..........94 XV-Board DO Channel Settings ..........95 7.2.2...
Page 6
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual Rules Setting ..................195 11.1 IF Condition Setting ..............197 ICP DAS Module ............... 198 11.1.1 Modbus Module ..............203 11.1.2 Power Meter ..............206 11.1.3 Microsoft Azure ..............207 11.1.4 11.1.5 IBM Bluemix ..............208 MQTT ................
Page 7
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual ....................312 Appendix III:Setup the GTM-203M-3GWA with PMD ........315 Appendix IV:The configuration setting of M-7000/DL module ......316 Appendix V:The SNMP Variables for PMC/PMD ........... 320 Appendix VI:The format of CGI Query command ........... 328 Appendix VII:Change the value of output channel of module or Internal Register by...
Page 8
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual List of Figures System Architecture ............... 2 Figure1-1 : PMC/PMD Login page ..............7 Figure3-1 : Main Page ..................8 Figure4-1 : Figure4-2 : System Function Area (login as a Administrator) ......9 System Function Area(login as a General user) ......... 9 Figure4-3 : Rules management toolbar (login as a Administrator) ......
Page 9
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual Figure5-18 : Historical Data Chart for power data ..........30 Figure5-19 : Historical Data Table for power data ..........31 Figure5-20 : Historical Data Report inquiry ............31 Figure5-21 : Daily Report for PM-3133 ............32 Figure5-22 : Daily Report for PM-3114 ............
Page 10
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual SNMP Setting Page ..............60 Figure6-9 : Figure6-10 : SNMP Manager List ..............61 The Address Setting for SNMP Manager ........61 Figure6-11 : Figure6-12 : The Working Model Setting for SNMP Manager ......61 Figure6-13 : Save the SNMP Manager Setting ..........
Page 11
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual Set up the No and Address of the power meter ........ 85 Figure7-8 : Figure7-9 : Select Modbus RTU Power Meter model ........85 Figure7-10 : Add the Modbus RTU Power Meter manually ........ 86 Add Modbus TCP Power Meter ............
Page 12
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual Figure7-46 : Discrete Input Setting Example for Modbus RTU Module ..... 117 Figure7-47 : Input Register Setting Page ............119 Figure7-48 : Input Register Setting Example for Modbus RTU Module ..... 120 Figure7-49 : Holding Register Setting Page ............ 122 Figure7-50 : Input Register Setting Example for Modbus RTU Module .....
Page 13
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual SMS Command list ............171 Figure10-11 : Figure10-12 : SNMP Trap Setting Page ............ 173 SNMP Trap Parameter Setting Page ........173 Figure10-13 : “Channel Data”Type Setting Page ........174 Figure10-14 : Example of “Channel Data” Type Variable Binding List..175 Figure10-15 : “User-Defined Data”...
Page 14
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual Holding Register condition setting page ........205 Figure11-9 : Figure11-10 : Power Meter condition setting page ........206 Microsoft Azure Connection Status condition setting ..... 207 Figure11-11 : Microsoft Azure Subscribe Message condition setting.... 207 Figure11-12 : IBM Bluemix Connection Status condition setting ....
Page 15
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual Bot Service action setting page ..........234 Figure11-47 : Figure11-48 : Re-boot system Action setting page ........234 Reset modem action setting page ......... 235 Figure11-49 : Data Logger action setting page ........... 235 Figure11-50 : Rule Status action setting page ..........
This easy-to-use solution will dramatically reduce the labor and cost spent on power monitoring and management system. PMC-523x/PMC-224x /PMD series products are including following models: Product Series PMC-523x PMC-224x Dimension...
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual together with PMC Data Server software or SCADA software, it allows collection and analysis of the power data. Figure1-1 : System Architecture With the built-in Web Server, it allows connection to PMC-523x/PMC-224x/PMD for power meter parameters and system settings via browser and allows viewing the real time or historical power data of the power meters.
Page 18
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual PMC-523x/PMC-224x/PMD to get real-time power data of the devices via Modbus TCP/RTU protocol. In addition, they also support the MQTT protocol to connect with the MQTT broker for the message publishing and subscribing mechanism, and the connection with the IoT service which Microsoft Azure and IBM Bluemix provide.
Page 19
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual Provides Timer & Schedule function for device operation control. Provides alarm message notification function via Email/SMS message/LINE Notify. Local Display for On-Site operations (PMD only) PMD is equipped with local side TFT LCD (with Touch Panel). It provides an easy way for viewing the power data and setting the system parameters on sites.
Page 20
PMC-523x/PMC-224x/PMD for conditional execution. In the following document, we use "PMC/PMD" to represent PMC-523x/PMC-224x/PMD series controllers. For the operations of the local display of PMD series, please refer to "PMD user manual for local operations".
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual 2 Before Installation Modify PMC/PMD‘s network settings to fit current network environment settings, and the default network settings of PMC/PMD is as follow: IP:192.168.255.1 Subnet mask:255.255.0.0 Gateway address:192.168.0.1 DNS Server address:8.8.8.8 (default: Google DNS Server)
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual 3 System Login When connect to PMC/PMD webpage server via Web browser (IE 8 / Firefox 3.6 / Chrome 14.0.8 version or above are recommended), in order to get a better operation experience, 1280x1024 resolution is recommended. The Login page of PMC/PMD is...
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual 4 System Main Page After login into the system, PMC/PMD default home page will be displayed, and will automatically read settings of the PMC/PMD to the webpage. Figure4-1 : Main Page PMC/PMD main page could be divided into 3 areas: A.
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual System function area System function area provides immediately access to the main functions of PMC/PMD, such as: system settings, system real-time information display, rule files management, etc, shown as below: Figure4-2 : System Function Area (login as a Administrator) System function area includes the following areas: A1.
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual as below: Figure4-5 : Rules management toolbar (login as a General user) The functions of the Rules management toolbar are as follow: On the left side of the Rules management toolbar, the user could move the mouse to the nickname field to give a nickname for this PMC/PMD in the nickname field for easy recognition.
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual PMC/PMD to the PMC/PMD. Figure4-8 : Confirm to save settings “Logout” button allows to log out the system, click on button and click “OK” to logout the system. Figure4-9 : Confirm to logout (The settings are saved)
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual easy recognition. 4.1.2 Real-time information area Real-time information area allows display of current free space and approximate number of days available to save of the microSD card of the PMC/PMD and the real-time system information, shown as below:...
Page 28
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual Chapter 11: Rule Setting If login as a general user, they are allowed to view real-time information on Main Page only; they also do not have the permission to edit the settings of the parameters and the rules.
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual Sub-function area Sub-function area will display detailed functions under the selected System function. The user could edit or review detailed function options in the Sub-function area. On the upper Sub-function area, the path of current function will be displayed to show the current function path.
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual Figure4-14 : Power data Overview page Power data overview page display the power data of the power meters that connected to the PMC/PMD. Depend on the requirement to select the desired classification of the power data to display the desired power data.
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual Figure4-16 : Display power data of the selected classification “Connection Status” will reveal the connection status between the power meter and PMC/PMD, the graphic indicators are as follow: : Online : Offline : Connecting...
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual 5 Main Page On the Main Page, 10 information display options are as follow: Power Meter Information, Power Data Information, Realtime Chart, Historical Chart, Historical Data Report, Historical Electricity Analysis, PUE Information, I/O Information, Event...
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual of the “Power Meter List”. The page refreshes every 20 seconds, the user could also click “Refresh” button to refresh the data immediately. Power Meter Information Overview includes the following sections: Figure5-2 : Power Meter Information Overview ...
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual Figure5-3 : The attribute of PM-3133 Power Meter Figure5-4 : The attribute of PM-3133-MTCP Power Meter Real Time Power Information In this section, it provides real time power data information of the selected Power Meter. For 3 phase power meter, it will display real time information of Phase A, Phase B and Phase C(Figure 5-5).For...
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual Figure5-6 : Real Time Power Information of PM-3114 Figure5-7 : Real Time Power Information of PM-3112 Reset Accumulated Value of the Power Meter When login as the Administrator, it allows to click on “Reset” to reset the value of kWh, kvarh, and kVAh to be 0 if required.
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual 5.1.2 Power Meter Statistics Information Overview On the Power Meter Statistics Information Overview page, the Demand Information section will display the Actual Demand, Forecast Demand, Contract Capacity, Hourly Maximum Demand, Daily Maximum Demand and Monthly Maximum Demand, etc.
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual 5.1.3 Other Information In the "Other" information page, users can view or setup the PT Ratio、CT Ratio、Phase Sequence、Wiring Mode、Voltage Mode and other specific parameters of the power meter. Figure5-9 : Power Meter Other Information Page 5.1.4...
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual Power Data Information Power data information can be displayed in two modes (Overview and Group Overview), user can change the viewing mode according to the requirements; more detailed information will be introduced in the following sections.
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual Figure5-12 : Change Display List Button Figure5-13 : The Power Meter List 5.2.2 Group Overview Power Data Information group overview mode allows display of power data of pre-set group of power meters (please refer to 6.7 Power Meter...
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual Select Group Select the group from the dropdown list in the “Select Group” field. If no group is pre-set, the inquiry operation will be disabled. Select Subgroup Select the subgroup from the dropdown list in the “Select Subgroup”...
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual Daily Accumulated Electricity, Daily Carbon Emissions, and Actual Demand. Please refer to Figure 5-15 for an example of Realtime Chart for “Power Meter Mode”. Each time the Realtime Chart displays only one power information classification. If a different power information classification is inquired, previously displayed chart will be closed automatically.
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual value. icon allows to hide the markers on the chart; click on button to show the markers on the chart. “Connection Status” will reveal the connection status of the power meter, the graphic indicators are shown as follow:...
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual Figure5-16 : Realtime Chart (Group Mode) There are three function icons on the upper area of the Power Meter Realtime Chart: The icon allows to pause the update of the chart, only the data within the 25 minutes will be displayed.
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual Historical Chart Historical Chart allows display of the value and chart of power data in historical trend. Select the power meter from the dropdown list of the Power Meter List, choose the classification from the dropdown list of the Data Classification and then specify the date from the dropdown list of the Date.
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual Historical Data Table are shown as below: Historical Data Chart The historical power data of specified classification will be displayed in historical chart. The user could select the range on the below region or drag and move on the chart to adjust the viewing range.
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual Figure5-19 : Historical Data Table for power data On the lower left of the Historical Data Table, there are 5 function icons. Go to the first page. Go to previous page. ...
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual When a single power meter is selected, a power data report of the specified power meter will be generated. If a power meter group is selected, a report of the "Total accumulative electricity" of all power meters in this group will be generated.
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual Figure5-22 : Daily Report for PM-3114 Figure5-23 : "Total Accu. Electricity" report for Power Meters Group Historical Electricity Analysis Historical Electricity Analysis can be done in 3 ways: Energy Usage Analysis by Trend, Energy Usage Analysis by Time and Energy Usage Breakdown by Circuit/Group.
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual Figure5-24 : Energy Usage Analysis by Trend Function Type: The user can select one of the following three options for electricity analysis: Energy Usage Analysis by Trend, Energy Usage Analysis by Time Period and Energy Usage Breakdown by Circuit/Group.
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual Figure5-25 : Inquiry by Group Mode User-defined: In user-defined mode, all power meters connected to the PMC/PMD will be listed. If no power meter is connected, the user will not be able to perform inquiry operation. The minimum loop/phase to be queried is 1 loop/phase.
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual Figure5-27 : PM-3114 Energy Usage Analysis Trend Chart On the upper left of the Energy Usage Analysis by Trend Chart, there are 4 function icons. Set the Energy Usage Analysis by Trend Chart to be default status.
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual Figure5-28 : Energy Usage Analysis by Time Period Function Type: The user can select one of the following three options for energy analysis: Energy Usage Analysis by Trend, Energy Usage Analysis by Time Period and Energy Usage Breakdown by Circuit/Group.
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual Figure5-29 : Time Histogram Chart for PM-3114 Loop 1 5.6.3 Energy Usage Breakdown by Circuit/Group The users could specify the data classification and the time range under this section, and then select the loop(s)/phase(s) to be inquired; the...
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual for energy analysis: Energy Usage Analysis by Trend, Energy Usage Analysis by Time Period and Energy Usage Breakdown by Circuit/Group. Data Classification: includes V (voltage), I (current), PF (power factor), Energy Usage (KWh), Carbon Emissions, and Maximum Demand.
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual PUE Information Power Usage Effectiveness(PUE) information can be displayed in two modes(Real-Time and History), users can change the viewing mode according to the requirement;more detailed information is as below: 5.7.1 Real-Time "Real-Time" overview mode allows display of the multiple PUE values which are calculated by "Total Facility Energy"...
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual Figure5-34 : PUE information - History(1) PUE List:All PUE options which are preset by users will be listed on the dropdown list of the PUE List, if no PUE option is preset, the inquiry operation will not be able to perform.
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual I/O Information The I/O Information page will display the real-time values of the Internal Registers of the PMC/PMD and the real-time I/O channels values of all I/O modules (including XV Board, M-7000, DL or IR Modules, Modbus RTU Modules and Modbus TCP modules) that are connected to the PMC/PMD.
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual I/O Realtime Chart I/O Realtime Chart allows display of real-time channel data of the I/O module in trend style. Select the I/O module from the dropdown list of the "I/O module List", the classification from the dropdown list of the "Type"...
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual 5.10 I/O Historical Chart I/O Historical Chart allows display of I/O channel historical data of the Data Logger in trend style. Specify the date from the dropdown list of the "Date" field, select the I/O channel from the "Channel Selector" field, then click on “Inquiry”...
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual Date The dates that are available for channel data retrieval will be displayed. Please note, if no log file is available, the inquiry operation will not be performed. Channel Selector All Channel of the User-Defined Data Logger will be list on the dropdown list of the "Channel Selector"...
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual 5.11 Event Log The Event Log page allows to view the list of system event logger information when login as the Administrator. Figure5-42 : Event Log information display The Event Log record including the following information: ...
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual 5.12 Polling Time Information Users can check the polling time of each modules and power meters which are connected with PMC/PMD currently. The "Polling Time Information Page" is as below: Figure5-43 : Polling Time Information The graphic indicator on the right side of the No.
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual Module Type “Module Type” includes 4 options : Power Meter, I/O Module, XV-Board and Other Information Module Name According to the selected “Module Type” option, the corresponding module name or information of “Module Name” will be listed.
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual Figure5-46 : Power Meter UID Information Page Users can click "Export" button to export the UID information as CSV file. 5.15 Ping Status Page It displays the latest Ping results of all Ping targets. The latest ping result is displayed in the “Result”...
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual 6 System Setting System Setting includes 6 options: Time Setting, Network Setting, SNMP Setting, Security Setting, I/O Interface Setting, Power Meter Group Setting and Other Setting. When you get into the System Setting page, the system settings information of this...
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual The user could view system setting information of PMC/PMD or perform firmware update on this page. For firmware update operations, please refer to 6.8 Firmware Update. Time Setting On the Time Setting page, it allows to set the time of PMC/PMD and Time Synchronization function.
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual Figure6-3 : Time Synchronization Setting Follow the steps below to set up Time Synchronization Setting: i. In the “Function Status” field, check “Enable” to enable the Time Synchronization function. ii. In the “SNTP Time Server” field, input the IP address or domain name of the SNTP Time Server.
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual Network Setting Network Setting allows making a change to network configuration, web server port setting, Modbus settings, Dynamic DNS setting and IoTstar Connection settging on the PMC/PMD. The following figure illustrates the configuration interface.
Page 70
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual Network Setting (LAN) Each time when the user enters this page, it will read and display current network configuration and port settings from the PMC/PMD. In the “Connection mode” field, please select the connection mode as “Obtain an IP address automatically (DHCP)”...
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual Network connection status between PMC-5231M-4GE(or 4GC)/PMC-5231M-3GWA and the Mobile Network. Please Note: In order to complete the connection to the Mobile Network, please remember to disable the PIN code setting of the SIM used in PMC-5231M-4GE(or 4GC)/PMC-5231M-3GWA.
Page 72
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual Follow the steps below to set up Dynamic DNS service: Click the services tabs on the right-top corner of “Dynamic DNS service”. System provides two items for selection as “Service 1” and “Service 2”. User can enable one Dynamic DNS service for normal status, or enable two Dynamic DNS services for the redundant service.
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual Click “Enable” of the “Function Status” to enable the network connection to the ICP DAS IoTstar. Two options : “User-built IoTstar” and ”IoTstar Trial” are available iii. for selection. ”User-built user select IoTstar”, please click in the “Server Address”...
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual in the “Server Address” field, click then enter the login username and password (require to apply in advance) in the “Username” and “Password” fields. PMC/PMD will login and connect to the “IoTstar Trial” by the information provided.
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual SNMP Setting The PMC/PMD provides SNMP(Simple Network Management Protocol) V1 and V2c to work with the SNMP Network Management software for monitoring the system data, power meter data and I/O module data. The SNMP Setting page allows you to enable or modify the settings of the SNMP function on the PMC/PMD.
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual v. In the “Contact” field, input the “Contact” string. vi. In the “Location” field, input the “Location” string, The SNMP Manager List is a list for all SNMP Managers which will interact with the SNMP Agent of PMC/PMD. Please follow the steps as below to perform the setting for SNMP Managers.
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual Please Note: If no "Read/Write" field on the list is enabled to accept the Read/Write commands, indicating that it will allow accepting the Read/Write commands from ANY SNMP Manager. iii. After completing the IP address and working model setting, please click button to add the SNMP Manager to the list.
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual Security Setting Security Setting allows user to change the password that is required when access to PMC/PMD. The user could also modify the settings of FTP Server and Idle Time. The Security Setting page is as follow:...
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual password is forgotten or lost, the PMC/PMD could send an email with the passwords (administrator and guest) to this email address, for more detailed information, please refer to Appendix Figure6-15 : Password Setting Page ...
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual Idle Time Setting After the administrator login into the PMC/PMD page, when the idle time exceeds the pre-set time interval (default is 10 minutes), the administrator will be automatically logout. The idle time could be set as Disable/10/20/30/60 minutes, after the setting is completed, click “Save”...
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual LAN:LAN connection is by default set for Modbus TCP Slave to connect HMI or SCADA. It can also be set for Modbus TCP Mater to connect Modbus TCP devices. COM1/COM2 :Reserved for Modbus RTU...
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual Connect to Modbus RTU slave device via COM Port. Figure6-20 : Function setting to connect to Modbus RTU slave device The settings steps are as below: i. In the “Baudrate” field, select the Baudrate from the dropdown list, the Baudrate of PMC/PMD and Modbus RTU slave device have to be set the same.
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual Connect to HMI (or SCADA) and Modbus TCP Slave device via LAN Figure6-21 : I/O Function setting about LAN The LAN function on PMC/PMD is by default set for Modbus TCP Slave to connect HMI or SCADA. User can also select the “Modbus TCP Master”...
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual Figure6-22 : Other setting page Contract Capacity Setting In this section, it allows to enable and set Contract Capacity. To enable the Contract Capacity function, click on “Enable” and input the Contract Capacity. Click “Save” button to save the settings. The Contract Capacity being set will be displayed on the System Setting main page.
Page 85
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual The setting procedure for electricity carbon emissions factor is as below: i Input the year user want to assign the carbon emission factor. ii Input the carbon emissions factor. Please assign the value according to the electricity carbon emissions factor published by the International Energy Agency (IEA) for each country.
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual Power Meter Group Setting The power meter group setting function allows user to create groups that contain specific loops/phases of power meters for easy group classification. These pre-set groups can be inquired in “Power Data Information” and “Historical Electricity Analysis”...
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual Figure6-25 : Group Setting Figure6-26 : Subgroup Setting ii Input the group/subgroup name and click to add this group/subgroup to the lists. Click “Close” button to return to group setting page. Figure6-27 : Subgroup Setting Window...
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual 6.7.3 Group and Subgroup configuration Figure6-28 : Configurations for Subgroup group/subgroup configurations done Group/Subgroup Setting page. Please select the group/subgroup first and click on the function button to perform the configurations: Change Name:Click the radio button in front of the group and click on “Change Name”...
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual Figure6-29 : Loops/Phases of subgroup Setting ii Select the loop/phase of the power meter and click to add this loop/phase to the lists. Click “Close” button to return to group setting page. Figure6-30 :...
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual Figure6-31 : Add Loops/Phases for Subgroup 6.7.5 Loop/Phase of group configuration Figure6-32 : Configurations for Loops/Phased of Subgroup The loop/phase of subgroup configurations can be done on the Power Meter Loop Setting page.. Please select the loop/phase first and click on the function button to perform the configurations: ...
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual Firmware Update PMC/PMD allows to update firmware via browser, after the update is completed; the PMC/PMD doesn’t require to reboot. Please follow the steps below: i. Please contact ICP DAS service to obtain the latest version of the PMC/PMD firmware file.
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual iii. Browse through to select the new firmware file and click “Open”. Figure6-34 : Firmware Update(2) iv. Click “Update” to update the firmware. Figure6-35 : Firmware Update(3) v. Click “OK” to start the firmware update, to cancel the firmware update, click “Cancel”.
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual vi. Updating the firmware Please note: when the firmware update process is started, please DO NOT close the update window or perform any system modification, or may result in unexpected failures. Figure6-37 : Firmware Update(5) vii.
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual Figure6-39 : Export / Import Setting page and the settings to be backed up Export PMC/PMD's Rule file: 1. After click the “Export Settings” button, the rule file would be stored in the default download path according to the browser's setting. If...
Page 95
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual 1. Click the “Import Settings” button and select the PMC/PMD's rule file to be imported from local PC to PMC/PMD. 2. After selecting the file to be imported, the user will be asked whether to abandon the current settings, or not.
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual 7 Power Meter & I/O Module Setting Meter / Module Setting page allows to perform settings of the power meters and I/O Modules that are connected to the PMC/PMD. After getting into the setting page, the...
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual Power Meter Setting On the “Power Meter Setting” page, it allows to set up the settings of the Modbus RTU and Modbus TCP power meters that are connected to the PMC/PMD. The Power Meter Setting page is shown as below:...
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual 7.1.1 Scan to add Modbus RTU Power Meters Perform “Scan” to automatically build a list of Modbus RTU power meters that are connected to the PMC/PMD. The steps are as below: i Before performing the scan of the power meters, please make sure...
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual Figure7-5 : Scanning the Power Meters v After the Scan operation is completed, a Power Meter List will appear (Figure 7-6). If the newly scanted module doesn’t match the module previously set on the same address, a window will appear (Figure 7-7), please select the actual device that are connected to PMC/PMD.
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual i No: The number will be the order that the power data of the Modbus RTU power meter being stored in the PMC/PMD Modbus Table. The range is 1~16. ii Address: The address will be the Modbus address of this Modbus...
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual Figure7-10 : Add the Modbus RTU Power Meter manually 7.1.3 Add Modbus TCP Power Meter Manually PMC/PMD allows connection to Modbus TCP Power Meters via Ethernet, the user could add the Modbus TCP Power meter to the list manually;...
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual iv Nickname: For user to define a nickname for this power meter, this nickname will be displayed on the “Power meter Information” and “Rule Setting” pages. Default setting will be the model of the power meter.
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual following section. Move Up: Click the radio button in front of the power meter and click on “Move Up” to move the power meter to upper order (upper index number (No)). Move Down: Click the radio button in front of the power meter and click on “Move Down”...
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual Figure7-15 : PM-3133 Setting Page The settings are as follow: Nickname:For user to define nicknames for each power meter, this nickname will be displayed on the “Power Meter Information” and “Rule Setting” pages.
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual seconds. Main Power Meter: When the “Set as main power meter” is selected, this power meter will be set as main power meter and the power data of this meter will be displayed on the Main Power Meter area on the “Power Data Overview”...
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual CT / Phase Nickname: For user to define nicknames for each CT (or phase), this nickname will be displayed on the “Power Meter Information” and “Rule Setting” pages. For single-phase power meter, the user could give nicknames to the CT1/CT2/ CT3/CT4.
Page 107
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual The settings are as follow: Nickname:For user to define nicknames for each power meter, this nickname will be displayed on the “Power Meter Information” and “Rule Setting” pages. Description: The Description field provides a space for the user to make a brief description of this power meter.
Page 108
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual CT3/ CT4. DO Attribute: Nickname:For user to define nicknames for each DO channel, this nickname will be displayed on the “Power Meter Information” and “Rule Setting” pages. Power On Value: Set up the initial value for the DO channels when the power meter is powered on.
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual XV-Board Setting (PMD series does not support this function.) XV-Board is used to connect with PMC. The setting page allows the user to set up the XV-Board that are connected to the PMC. The XV-Board Setting...
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual Figure7-19 : XV-Board DI attribute setting page The settings are as follow: Nickname:For user to define nicknames for each I/O channel, this nickname will be displayed on the “I/O Information” and “Rule Setting” pages.
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual Figure7-20 : XV-Board DO attribute setting page The settings are as follow: Nickname:For user to define nicknames for each I/O channel, this nickname will be displayed on the “I/O Information” and “Rule Setting” pages.
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual DI Status Mapping: When “DI Status Mapping” is selected, the status of the DI channel with the same channel number on the XV-Board will be copied to the DO channel. For example, when the “DI Status Mapping” is enabled on DO0, when the DI0 status is ON, DO0 will set to be ON, and when the DI0 status is OFF, DO0 will set to be OFF as well.
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual The IF Condition will use this already-adjusted value in the evaluation operation, and the AI value retrieved from the “I/O Information” page or Modbus Table via PMC-523x would be the adjusted value. The default value for MAX and MIN is 0, it means the Scale function is disabled.
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual AI<10mA, THEN DO=ON, ELSE DO=OFF, that means, when AI receives a signal which is lower than 10mA, the DO channel will change to ON immediately, however, when the AI channel value exceed 10mA, the DO channel will not...
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual After all settings of the channels are completed, click “OK” button to return to XV-Board Setting page. 7.2.4 XV-Board AO Channel Settings The XV-Board AO Channel Setting page is shown as follow (using PMC-5231+XV310 as an example):...
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual I/O Module Setting PMC/PMD allows connections to ICP DAS M-7000/DL/IR modules. It also supports standard Modbus RTU or Modbus TCP I/O modules. The I/O Module Setting page allows user to add Modbus RTU or Modbus TCP I/O modules that are connected to the PMC/PMD to the list.
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual 7.3.1 Scan to Add ICP DAS M-7000/DL Modules The user could use Scan function to add ICP DAS M-7000/DL Modules to the PMC/PMD, the steps are as below: (Please Note: The ICP DAS IR modules does not support the scan function, please add it manually.)
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual Figure7-29 : Scanning the M-7000/DL modules iv After the Scan operation is completed, an M-7000/DL module list will appear (Figure 7-30). If the newly scanted module doesn’t match the module previously set on the same address, a window will appear (Figure 7-31), please select the actual device that are connected to PMC/PMD.
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual 7.3.2 Add Modbus RTU Module Manually (or M-7000/DL/IR Module) In addition to perform Scan operation to automatically add M-7000/DL /IR modules to the list, the user could also add the Modbus RTU module (or M-7000/DL/IR module) manually one by one, the steps are...
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual v Retry Interval: The time interval to wait for PMC/PMD to repeatedly send command again when PMC/PMD sends command to the Modbus RTU module and get no response. The unit will be second. the setting range will be 3 ~ 65535 seconds.
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual Figure7-36 : Add the Modbus RTU Power Meter manually 7.3.4 I/O Module List Interface After the Modbus RTU I/O module or Modbus TCP I/O module are added to the I/O Module list via auto scan or manual work, the Modbus...
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual front of the pre-set Modbus I/O module and then click on “Copy”, a new Modbus I/O module (in sequence) will be added to the list and the settings of the old Modbus I/O module will be copied to this newly added Modbus I/O module.
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual The settings interfaces of the DI, DO, AI and AO channels on the M-7000/DL/IR Module are as below: The DI channel setting for M-7000 module The M-7000 module DI channel setting interface is shown as...
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual Please Note: 1. For M-7000 modules, the counting mode of the DI channel counter is Falling. 2. To set up the default value of the DI channels on M-7000 modules, please use DCON Utility to set the value.
Page 125
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual the status of the DI channel with the same channel number on the M-7000/DL module will be copied to the DO channel. For example, when the “DI Status Mapping” is enabled on DO0, when the DI0 status is ON, DO0 will set to be ON, and when the DI0 status is OFF, DO0 will set to be OFF as well.
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual Figure7-40 : M-7000/DL AI Channel Setting Page The settings are as below: Nickname:For user to define nickname for each I/O channel, this nickname will be displayed on the “I/O Information” and “Rule Setting” pages.
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual The AO channel setting for M-7000 module The M-7000 module AO channel setting interface is shown as below (using M-7024 as an example) Figure7-41 : M-7000 AO Channel Setting Page The settings are as below: ...
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual engine, it allows to perform automation control operation on the modules. And with SCADA software, it also allows monitoring and control of the Modbus RTU modules which connect with the PMC/PMD. The Modbus RTU Slave Module setting page is shown as...
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual command to the Modbus RTU module and wait for the response, the unit will be ms. The setting range will be 1-10000 ms. Retry Interval: The time interval to wait for PMC/PMD to repeatedly send command again when PMC/PMD sends command to the Modbus RTU module and get no response.
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual The Modbus Address of Data Model Modbus RTU Slave Modules Coil Output 0xxxx Discrete Input 1xxxx Input Register 3xxxx Holding Register 4xxxx Start Address: Allows setting up the starting address of Coil Output (0x) on the Modbus RTU Slave module you would like to retrieve.
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual To modify the starting address or quantity setting, please click on the setting block and input the setting. Click “OK” for modification or click “Remove” to remove the setting. If the user wants to assign a Nickname for the address blocks, the user can click on the “Nickname Setting”...
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual The settings are as follow: Data Model: PMC/PMD offers 4 Data Model selections to match the Modbus RTU Slave module configuration. Please refer to the above section “The Coil Output Setting of Modbus RTU Module”...
Page 133
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual To modify the starting address or quantity setting, please click on the setting block and input the setting. Click “OK” for modification or click “Remove” to remove the setting. If the user wants to assign a Nickname for the address blocks, the user can click on the “Nickname Setting”...
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual Figure7-47 : Input Register Setting Page The settings are as below: Data Model: PMC/PMD offers 4 Data Model selections to match the Modbus RTU Slave module configuration. Please refer to the above section “The Coil Output Setting of Modbus RTU Module”...
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual If users select “32-bit Signed Long”, “32-bit Unsigned Long”, or “32-bit Floating Point”, the option “Inverse(Big Endian)” will appear. Enable “Inverse(Big Endian)” to receive the data in big endian format correctly. After finishing the “Start Address”, “Data Number”, and “Type”...
Page 136
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual on the setting block to perform the modification. The user could also modify Type, Scale Ratio, Offset and Deadband on this interface. The Scale Ratio setting and Offset setting allows user to transform the Input Register value in this block by linear transformation.
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual After all Input Register settings of the Modbus RTU module are completed, click “OK” button to save the changes. The Holding Register Setting of Modbus RTU Module The Modbus RTU Slave module Holding Register Setting page is...
Page 138
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual Holding Register of Modbus RTU module. The 6 Data Type options are “16-bit Signed Integer”, “16-bit Unsigned Integer”, “16-bit Hex”, “32-bit Signed Long”, “32-bit Unsigned Long”, and “32-bit Floating Point”. If the “16-bit HEX” option is...
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual Figure7-50 : Input Register Setting Example for Modbus RTU Module To modify the starting address or quantity setting, please click on the setting block to perform the modification. The user could also modify Type, Scale Ratio, Offset and Deadband on this interface.
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual TCP protocol, it enables to read or write 4 types of Modbus data (Coil Output, Discrete Input, Input Register and Holding Register) from the Modbus TCP Slave modules. And by PMC/PMD IF-THEN-ELSE rule engine, it allows to perform automation control operation on the modules.
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual retrieve the I/O channel data of this Modbus TCP module, the setting range will be 0 ~ 65535 seconds. Polling Timeout: The time interval for PMC/PMD to send command to the Modbus TCP module and wait for the response, the unit will be ms.
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual 8 Logger Setting The Logger Setting function of the PMC/PMD provides recording of the power data from power meters and the I/O channel data from I/O modules. It includes Power Data Logger, I/O Data Logger and User-Defined Data Logger. The Power Data...
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual Data Logger Setting On the Data Logger Setting page, the user could enable the Power Data Logger, I/O Data Logger or User-Defined Data Logger of the PMC/PMD if required. The Power Data Logger allows recording the power data of the...
Page 144
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual dropdown list of the “Log Mode”. If “Average” is selected, the system will record the average value of the power data during the time interval set in “Log Interval”. If “Instantaneous” is selected, the system will record the instantaneous value of the power data when the time reaches the time interval set in “Log Interval”.
Page 145
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual Select the “Source”, “Module” and “Channel” from the dropdown list and click “Insert” to add channel value encoded string into the “Data Format” content. The system will record the data the user pre-set in the Data Format, and will save the real data values in the data log file.
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual Data Logger and User-Defined Data Logger. The data logger files of Power Data Logger, I/O Data Logger and User-Defined Data Logger all are saved in the micro SD card. If the micro SD card’s free space is less than the required space of one day...
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual FTP Upload Setting Power Data logger files, I/O Power Data logger files and User-Defined Data logger files can be upload to remote FTP server of the manage center via FTP protocol. The FTP Upload Setting page allows to set up parameters for...
Page 148
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual enable the Upload Event Log function, check “Upload Event Log” field. And then select the Frequency from the dropdown list of the “Frequency” field. The Frequency can be set as: once a day, once a week or once a month.
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual Report Sending Setting Page The power information report can be sent to the user via email, and the relevant parameters of the function can be set in the "Report Sending Setting Page". 8.4.1 Sending Setting The "Send Setting"...
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual The "Re-send Function" can send the corresponding historical power information reports to recipients immediately by the date user assign. The settings page is shown as below: Report Sending Setting page – Sending Setting Figure8-6 : Follow the steps below: i.
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual The Path of Data Log File The data logger files of PMC/PMD will all be saved in the microSD card. The following section will explain the path of the data logger files saved in the microSD card: ...
Page 152
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual Daily Report Log \ 192.168.100.20_502_00D3 [3112]1 \ 2013-05-23Rpt.csv Monthly Report Log \ 192.168.100.20_502_00D3 [3112]1 \ 2013-05Rpt.csv 為該電表的 ID; 192.168.100.20_502_00D3[3112]1 192.168.100.20_502_00D3[3112]1 is the ID of this power meter. 192.168.100.20 indicates the connection IP of the power meter;...
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual EventLog \ Event-2013-05-23.log 20130523 indicates that the first event recorded in the Event Log file is starting from May 23, 2013 The format of the Power Data Logger file The power data logger files generated are in CSV format. Each line represents one record;...
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual Phase A/CT4 [ Voltage, Current, kW, kvar, kVA, PF, kWh, kvarh, kVAh, Daily tot. Electricity , Current demand( Phase B/CT5 (kWh) 15/30/60 mins) Voltage, Current, kW, kvar, kVA, PF, kWh, kvarh, kVAh, Daily tot.
Page 155
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual PM-2134 / PM-3112(-MTCP) / PM-3114(-MTCP) Daily Report Index of hour, Date, Power meter ID, CT1 [ Timing of hourly max kW, hourly max kW, Hourly total Electricity, Average hourly PF, Average hourly current, Average hourly voltage, Average hourly kVA, Average hourly...
Page 156
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual hourly kvar], [Timing of hourly max kW, hourly max kW, hourly total Electricity, Average hourly PF, Average hourly current, Average hourly voltage, Average hourly kVA, Average hourly kvar], Average/Total [Timing of hourly max kW, hourly max kW, hourly total Electricity,...
Page 157
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual daily current, Average daily voltage, Total daily kVA, Total daily kvar] ..Submeter 8 CT22 [Timing of daily max kW, daily max kW, daily total Electricity, Average daily PF, Average daily current, Average daily voltage, Average daily kVA, Average daily...
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual The Format of I/O Data File The I/O data logger files generated are in CSV format. Each line represents one record; each field in the line is separated by a comma. The data sequences from left to right in the line of the I/O data are as follows: 2013/06/01,12:35:00,XXXX,…,…,…,Period...
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual 9 IoT Platform Setting The IoT Platform Setting function of the PMC/PMD allows to build a connection to Microsoft Azure or IBM Bluemix directly. It can also connect to MQTT Brokers like Amazon CloudMQTT. Based on the IoT Platform Setting function, PMC/PMD can...
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual Microsoft Azure Setting On the Microsoft Azure Setting page, the connection to Microsoft Azure IoT Cloud Platform can be built if required. The setting page is shown as below: Figure9-1 : Microsoft Azure Setting Page Follow the steps below: i Check “Enable”...
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual v To verify whether the SAS Token setting is correct, click “Testing” in the “Connection Testing” field, then PMC/PMD will try to connect Microsoft Azure with the SAS Token setting, and reply the connection status.
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual power data (and I/O channel values) of the module will be added in the Publish Message List. If the user click the "JSON Format" check box, the content of the Publish Message will be packaged in JSON format; if the “JSON”...
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual Figure9-4 : Microsoft Azure Subscribe Topic setting page xiii In the “Variable Name” field, user can input the name of the variable which is defined in the message of the Subscribe Topic. After completing the settings, click the "Add" button to add the variable. For...
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual IBM Bluemix Setting On the IBM Bluemix Setting page, the user could enable the connection to IBM Bluemix IoT Cloud Platform if required. The setting page is shown as below: Figure9-5 : IBM Bluemix Setting page Follow the steps below: i Check “Enable”...
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual iii The value in “keep alive Time” field defines the maximum amount of time in second that pass away without communication between the PMC/PMD and IBM Bluemix. The “keep alive interval” enables IBM Bluemix to detect if the connection to the PMC/PMD is no longer available without having to wait for the long TCP/IP timeout.
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual completing the setting, click the "Add" button to add the variable. For the message the PMC/PMD receives from IBM Bluemix is based on JSON format, the PMC/PMD can also get the corresponding value of the variable from the received message.
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual Figure9-7 : MQTT Setting Page (Broker) The settings steps are as below: i. Click the “Broker Setting” tab on the right-top corner of “MQTT Setting Page”. ii. Click on “Add new MQTT Broker” to add the new MQTT Broker.
Page 168
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual iv. Check “Enable” or “Disable” in the “Initial Status” field to enable the initial connection status with the Broker. If the user clicks “Enable”, it means the PMC/PMD will start the communication with the Broker after it is powered on.
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual xiii. The value in "Periodical Publish Interval" field defines the time interval (in second) to send all Publish Topics with the “Periodical Publish” attribute automatically and periodically. If the value of the "Periodical Publish Interval" field is 0, it means the “Periodical Publish”...
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual Figure9-10 : Publish Message Setting Page xvii. Input a name in the “Nickname” field and you could also input the description of this Publish Message in the “Description” field. xviii. In the “Message Type” field, select the “Channel Data” to prepare a Publish Message with the power data or I/O channel value.
Page 171
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual The user can select “User-Defined Data” in “Message Type” field to edit the Publish Topic and its binding message on the free style editing interface. The user interface is shown as below. xix. In the “QoS” field, user can select 0, 1, 2 for the QoS(Quality of Service) setting for the Publish Message.
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual The Interface will be shown as below: Figure9-11 : Subscribe Topic Setting Page xxv. Input a name of the Subscribe Topic in the “Nickname” field, and you could also input the description of this Subscribe Topic in the “Description”...
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual Figure9-12 : MQTT Topic Import/Export setting page All MQTT Publish Topics and Subscribe Topics that the PMC/PMD is using now will be shown in the setting page. Click the “Export” button will collect all topics into the “topics.csv” file. The format of the “topics.csv”...
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual Figure9-14 : The Import of MQTT Topic IoTstar Real-Time Data Sending Setting IoTstar can receive the real-time power data (and I/O data) uploaded by PMC/PMD, and import these data into the database it created. The setting...
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual Follow the steps below: i. In the “Function Status” field, check “Enable” to enable the Real-Time data upload operation. ii. In the "Add Channel" section, select the “Interface”, “Module” and “Channel” from the dropdown list and click “Insert” to add the power meter loop or I/O channel into the “Channel List"...
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual Follow the steps below: i. To enable PMC/PMD's historical data upload operation, users need to enable Data Logger function of PMC/PMD first. More detailed setting information please refers to the section”8.1 Data Logger Setting”.
Page 177
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual ii. Input name in the “Name” field and you could input the description of this LINE message in the “Description” field. iii. Enter the message content in the “Content” field. PMC/PMD provides encoded strings for users to add current I/O channel value, power data or Internal Register value into the messages.
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual 10 Advanced Setting Advanced Setting provides additional features and allows you to perform more setting on the PMC devices. Click on the Advanced Setting button, a column of buttons will appear on the left of the page: ...
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual Figure10-1 : Email setting page The settings steps are as below: i Click on “Add new email” to add a new email setting. After clicking the “Add new email”, a setting page will appear, input name in the “Name”...
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual Figure10-3 : Email setting page(SMTP Server) iv Input the Port number, the default port number is set as 25. If the SMTP server requires account and password validation, please select the “Enable” checkbox, and continue steps vi~viii to login into the SMTP server.
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual After complete Email Address setting, continue to input Email Content setting. Enter the email subject in the “Subject” field. The Email Content Setting page is shown as below: Figure10-5 : Email setting page(Email Content) xiii Enter the content in the “Content”...
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual 10.2 SMS Setting PMC-5231M-4GE/PMC-5231M-4GC/PMC-5231M-3GWA/PMC-2241M/P MD offers SMS Alarm message sending and SMS Command receiving functions (PMD must equip ICP DAS GTM-203M-3GWA modem. Please refer to Appendix III for detail). For SMS Alarm function; it allows to send pre-set SMS alarm message to specific phone numbers.
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual Figure10-7 : SMS Setting Page (2) iv Input name in the “Name” field and you could also input the description of this SMS Alarm in the “Description” field. v In the “Phone Number” section, click on “Add’’ to input the phone numbers to receive the SMS Alarm messages.
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual radio button in front of the SMS Alarm, and then click on “Setting” to modify the settings. x To copy the settings of a pre-set SMS Alarm to the new SMS Alarm, please click the radio button in front of the pre-set SMS Alarm and then click “Copy”, a new SMS Alarm will be added to the list and...
Page 185
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual the phone numbers you would like to authorize to send SMS commands to PMC/PMD. Keep on clicking “Add” to add all phone numbers to send the SMS commands to PMC/PMD, click “Remove” to remove the phone numbers you want to delete.
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual Figure10-9 : SMS Command Setting for GET Command Figure10-10 : SMS Command Setting for SET Command vii Click on “OK” to confirm the setting and leave the setting page. viii Repeat steps v~vii to complete settings of all SMS Command setting.
Page 187
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual On Figure 10-11, taking the first SMS Command on the list as an example, when user send message “DATA” PMC-5231-3GWA, PMC-5231-3GWA will send back the data of DI0, DI1, & DI2 of the XV-Board, the Total/Average value of the kW from module PM-2133(2) on COM3, and value of Internal Register 1 to the command sender.
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual 10.3 SNMP Trap Setting SNMP Trap function allows PMC/PMD to initiative sending of the system data, power meter data and IO channel data to the SNMP Manager in real time automatically when unusual events occur; so that the SNMP Manager can respond immediately with corresponding operations.
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual name of the SNMP Trap in the “Nickname” field and you could also input the description of this SNMP Trap in the “Description” field. iv Input the Specific ID value of the SNMP Trap in the “Specific ID”...
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual Figure10-15 : Example of “Channel Data” Type Variable Binding List vii You can select the “User-Defined Data” as the variable type. The setting page interface will be shown as below: Figure10-16 : “User-Defined Data” Type Setting Page Set up the content in the “User-Defined Data”...
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual Figure10-17 : “User-Defined Data” Interface in Edit Mode Input your message in the “User-Defined Data” field, and then select the “Source”, “Module” and “Channel” from the dropdown list and click “Insert” to add channel value encoded string into the “User-Defined Data”...
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual Figure10-18 : “User-Defined Data” Interface in View Mode After completing the setting, click the “OK” button to save the parameters and variable bindings setting, and return to the SNMP Trap Setting Page Figure10-19 : SNMP Trap setting with variable bindings list...
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual added SNMP Trap. ix To remove a pre-set SNMP Trap, please click the radio button in front of the pre-set SNMP Trap and then click “Remove”. After you finishing all the SNMP Traps creation and setting, click “Save”...
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual Figure10-21 : LINE Notify Message Setting page (2) iii. Input name in the “Name” field and you could also input the description of this LINE message in the “Description” field. iv. Enter the message content in the “Content” field. LINE message provides an encoded string for you to add current power data, I/O channel data or Internal Register data into LINE messages.
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual v. In the “Chat Room” field, please specify the Chat rooms which will receive the message PMC/PMD send. PMC/PMD can send the messages to multi-chat rooms simultaneously. Users can directly click on the “Add new Chat Room” to connect with a new chat room, please refer to the section “10.4.2 Chat Room...
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual Figure10-24 : LINE Notify Chat Room Setting page (1) The settings steps are as below: i. Click “Add new chat room”, the LINE Notify Connection Setting page will appear as below. Input the Client ID and Client Secret of the applied service and click the “Send”...
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual Figure10-26 : LINE Notify Chat Room Setting page (3) iii. After login, select this account(one-to-one) or a group under this account which PMC/PMD will connect to. Figure10-27 : LINE Notify Chat Room Setting page (4) iv.
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual v. After you finish all the LINE Notify Chat Room settings, click “Save” button to save the settings. Please Note: The limit of LINE Notify service to each chat room: The number of text message: 1000 per hour.
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual Internal Register:Assign the period interval as the value of selected internal register. Please note: The user must setup internal register before using internal register as timer period. Please refer to ch 10.8 Internal Register Setting to setup internal register.
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual Figure10-31 : Timer setting page(Internal Register) vii To copy the settings of a pre-set Timer to the new Timer, please click the radio button in front of the pre-set Timer and then click “Copy”, a new Timer (in sequence) will be added to the list and the settings of the old Timer will be copied to this newly added Timer.
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual After clicking the “Add new schedule”, a setting page will appear, input name in the “Name” field and you could also input the description of this schedule in the “Description” field. iii Select Mode to be “Calendar” or “Repeat”.
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual Time Range. (c.) On the calendars, click to toggle highlight on the dates you’d like to execute or not execute the operations for this Schedule. If the date shows a light green background, it indicates the date is “In Range”...
Page 203
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual (b.) In the “Exception Date(s)” selection, click on “Add” to add the date(s) that is/are not going to execute the schedule. Click “Remove” to remove a pre-set Exception Date. (c.) In the “Time Range(s)” section, click “Add” to add new Time Range to execute this schedule.
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual 10.7 PUE Setting PMC/PMD provides 10 PUEs; The configuration is shown as below: Figure10-35 : PUE Setting Page(1) The settings steps are as below: i Click on "Add new PUE" to add a new PUE option.
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual Figure10-36 : PUE Setting Page(2) ix Click on “OK” to confirm the setting and leave the setting page. x Repeat steps i~ix to complete settings of all PUE setting. xi To modify the settings of a pre-set PUE, please click on the radio button in front of the PUE, and then click on “Setting”...
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual 10.8 Internal Register Setting PMC/PMD provides 70 Internal Registers; the Internal Registers of No.51 to No.70 provide the "Retain Variable" mechanism. It means that the data inside these Internal Registers will be retained even the PMC/PMD is in Power Off status.
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual Register. Please Note: there are up to 70 Internal Register can be enabled, if the name of the register is not inputted, the name will be automatically set as “Internal Register#”(#is the number of the register), the default initial value will be set as 0.
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual 1. Do not modify the channel value encoded string when you are editing the formula. It may cause failures when PMC/PMD reads the power data or I/O channel value. 2. Before you click the “Test” button, please confirm that the power meter and I/O module setting is saved to PMC/PMD if you use the power data or I/O channels in the formula.
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual name in the “Nickname” field and you could also input the description of this Ping in the “Description” field; shown as below: Figure10-40 : Ping List Page In the “Target” field, enter the IP or the domain name of the target to be pinged.
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual 11 Rules Setting After finishing all Advanced Setting configurations, you can start to edit IF-THEN-ELSE rules. Click the “Rules Setting” button, a list of rules will be displayed on the left side of the page, and at the right side of the page will show detailed content of each rule that was previously defined.
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual Figure11-2 : Rules setting page Nickname: Input name in the “Nickname” field and you could also input the description of this Rule in the “Description” field. Status: Select “Enable” or “Disable”. If you select “Enable”, the rule will be executed after being downloaded.
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual Setting: to edit a pre-set function component, click on to get in to the setting page of the function component. Copy: to copy a pre-set function component, click on to generate a new component with the same pre-set component settings.
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual options for I/O channel information (AI, DI, Discrete Input, Coil Output, Input Register and Holding Register) or power data on these modules will be automatically displayed on the dropdown list. To include subjects other than modules mentioned above in the IF Condition statement;...
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual iii Click “OK” button to confirm the settings and return to the Rule settings page. 11.1.1.2 DI Counter DI counter value from XV-Board/M-7000 module can be used as evaluation criteria for IF condition statement; the editing page for...
Page 215
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual used as evaluation criteria; select the number of the Internal Register from the dropdown list. DI Counter: The DI channel counter value from other ICP DAS modules(such as: XV-Board/M-7000) could be used as evaluation criteria;...
Page 216
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual Holding Register: The Holding Register value from other Modbus RTU/TCP Slave modules could be used as evaluation criteria; select the module and channel from the dropdown list to specify which channel value will be used.
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual Bluemix: The value of the Bluemix received paremeter could be used as evaluation criteria; select the command and the variable name from the dropdown list to specify which variable will be used. Please Note: The content of received MQTT subscribe...
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual Specify the module and channel from the dropdown list of the “Module & Channel” section that you are going to include its value in the IF condition statements. ii Set up the expression statement for this channel value. Select an operator from “=”,”>”,”<”,”>=”...
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual Rule settings page. 11.1.2.2 Coil Output Coil Output channel value from Modbus TCP/RTU Slave module can be included in the IF condition statements; the editing page for Coil Output Condition Setting is shown as below:...
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual IF condition statements. ii Set up the expression statement for this Input Register address value. Select an operator from “=”,”>”,”<”,”>=” or “<=”. iii And then specify the evaluation value. If this Input Register value match the evaluation criteria, the result of this condition evaluation will be “true”.
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual information. v Click “OK” button to confirm the settings and return to the Rule settings page. 11.1.3 Power Meter The power data of the Power Meter could be used as evaluation criteria; the power data options are as follow: Basic Value, Statistical Value and Others Informations.
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual information. v Click “OK” button to confirm the settings and return to the Rule settings page. 11.1.4 Microsoft Azure Click on Microsoft Azure, 2 options will appear as the following: " Connection Status" and " Subscribe Message".
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual i Specify the variable from the dropdown list of “Variable Name” field that you are going to include it in the IF condition statements. ii Set up the expression statement for the content of this Subscribe Topic.
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual Bluemix can be used in the IF condition statements; the editing page for IBM Bluemix Subscribe Message condition setting is shown as below: Figure11-14 : IBM Bluemix Subscribe Message condition setting Follow the steps below: i Specify the Command and Variable from the dropdown list of “Command Name”...
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual Figure11-15 : Broker Connection Status condition setting Follow the steps below: i Specify the Broker from the dropdown list of “Broker” field that you are going to include its connection status in the IF condition statements.
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual Subscribe Topic for condition evaluation. Please refer to “11.1.1.2 DI Counter” section for more detailed information. iv Click “OK” button to confirm the settings and return to the Rule settings page. 11.1.7 Connection Status Connection Status can be included in the IF condition statements;...
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual Follow the following steps: i Select the timer that you are going to use its status as evaluation criteria for IF condition statement. Specify the timer from the dropdown list of the “Timer” field.
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual Figure11-20 : Mobile Network Signal Strength condition setting page Follow the steps below: i Select the unit that you are going to use for IF condition statement. The interface provides dBm and Percent(%) for selection.
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual condition statement; the editing page for SD Card Status Condition Setting is shown as follow: Figure11-22 : SD Card Status condition setting page Follow the steps below: i When the status of micro SD Card appears irregular (micro SD Card is not detected or the space is less than 100MB), the result of this condition evaluation will be “true”...
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual statement; the editing page for Internal Register Condition Setting is shown as follow: Figure11-24 : Internal register condition setting page Follow the steps below: i Select the Internal Register that you are going to use the value as evaluation criteria for IF condition statement.
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual dropdown list of “No.” field. ii Set up the expression statement for this PUE value. Select an operator from “=”,”>”,”<”,”>=” or “<=”. iii And then specify the evaluation value. If this PUE value match the evaluation criteria, the result of this condition evaluation will be “true”.
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual 11.2 THEN/ELSE Action Setting To add a THEN/ELSE Action, please select and set the Action from the dropdown list in the “Add a new Action” field under the THEN/ELSE Action setting section. ICP DAS Module ...
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual THEN/ELSE Action are as follow: One-Time: when the IF Condition is TRUE, this Action will be executed once and only once. This Action will not be executed again until the IF Condition turns to be TRUE again.
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual Figure11-28 : DO action setting page Follow the steps below: Specify the module and channel from the dropdown list of the “Module & Channel” section. ii Specify the output value of DO Channel from the dropdown list of the “Status”...
Page 235
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual Follow the steps below: From the dropdown list of the “Module & Channel” field, select the AO channel to execute actions. ii Specify the Operator to be “=”, “+=”, or “-=” from the dropdown list in the “Operator” field. The 3 operators are as follow:...
Page 236
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual AO: using AO channel values from XV-Board /M-7000, select the module and channel from the dropdown list to specify which channel value will be used. Input Register: using value of Input Register from Modbus...
Page 237
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual the broker and the subscribe topic from the dropdown list to specify which value will be used. Azure: using the value of Azure received paremeter, select the parameter from the dropdown list to specify which value will be used.
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual Rule settings page. 11.2.2 Modbus Module Click on “Modbus Module”, 2 options will appear as the following: Coil Output and Holding Register. 11.2.2.1 Coil Output You can execute an action to change the status of Coil Output of Modbus TCP/RTU module in the THEN/ELSE Action statement;...
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual Figure11-31 : Holding Register action setting page Follow the steps below: Select the module and address of the Holding Register from the dropdown list of the “Module & Address” section. ii Specify the Operator in the “Operator” field. The 3 operators are as follow:...
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual Figure11-32 : Power Meter Relay Action setting page Follow the steps below: i From the dropdown list of the “Power Meter & Channel” field, select the Power Meter module and Channel. ii Specify the output value of Power Relay from the dropdown list of the “Status”...
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual PMC/PMD to be “Disable” or “Enable” from the dropdown list of the “Status” field. ii Click “OK” button to confirm the settings and return to the Rule settings page. 11.2.4.2 Publish Message You can publish messages to Microsoft Azure when executing a THEN/ELSE Action statement;...
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual “Variable Name” field. When this action is executed, PMC/PMD would reset the content of the variable, and the evaluation result of the IF statement which is associated with the variable will be verified again.
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual Figure11-37 : IBM Bluemix Publish Message action setting Follow the steps below: i Select a pre-set Publish message from the dropdown list of the “Message” field. The Publish message will be displayed for you to verify if this is the message you are going to send to.
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual Click on “MQTT”, 3 options will appear as the following: “Broker Function”, “Publish Message” and “Reset Topic”. 11.2.6.1 Broker Function User can execute an action to change the function status of MQTT Broker in the THEN/ELSE Action statement; the editing page is...
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual i Select a pre-set MQTT Publish Topic message from the dropdown list of the “Broker” and “Message” fields. The MQTT Publish Topic message will be displayed for you to verify if this is the MQTT Publish Topic message you are going to send to.
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual Figure11-42 : Timer action setting page Follow the following steps: i Select the pre-defined Timer from the dropdown list of the “Timer” field. Please note: the Timer you select has to be created in Advanced Setting.
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual ii Click “OK” button to confirm the settings and return to the Rule settings page. 11.2.9 SMS Alarm You can send a specific SMS Alarm message when executing a THEN/ELSE Action statement. The setting page is show as below:...
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual Figure11-45 : SNMP Trap Action Setting Page Follow the steps below: i In the “Trap” field, specify the SNMP Trap you want to execute in Action from the dropdown list. Please note, the SNMP Trap you select has to be the pre-set SNMP Trap in the "SNMP Trap Setting...
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual ii Click “OK” button to confirm the settings and return to the Rule settings page. 11.2.12 Bot Service You can send a specific Bot Service message to the LINE personal account which is bound with IoTstar when executing a THEN/ELSE Action statement.
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual The Reset modem action would power off and then power on the modem again to force the modem back to the initial status, and then the mobile connection would be re-started if the mobile network connection is enabled.
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual Figure11-51 : Rule Status action setting page Follow the steps below: i Specify the Rule (It has to be a previously saved Rule) that is going to be changed in the Action Condition statement from the dropdown list of the “Rule”...
Page 252
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual original Internal Register value plus the value in “Value” field. “-=”:Indicate assign the new Internal Register value as the original Internal Register value minus the value in “Value” field. “*=”:Indicate assign the new Internal Register value as the original Internal Register value times the value in “Value”...
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual Appendix I:Modbus Address Table PMC/PMD allows SCADA software or HMI device to retrieve the power data, I/O channel data and system information via Modbus TCP/RTU protocol. PMC/PMD register addresses are specified according to Modbus register mapping tables (more detailed information will follow).
Page 254
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual PMC/PMD Modbus Address Table Please note:Because each PMC/PMD product model provide different COM Port capability. So please verify the mapping information between RS-485-1 & RS-485-2 and actual COM Port as below. RS-485-1 RS-485-2 PMC-5231/PMC-2241M...
Page 255
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual 1000~2199 Module/Power Data of RS-485-1 (Index=1) 2200~3399 Module/Power Data of RS-485-1 (Index=2) 3400~4599 Module/Power Data of RS-485-1 (Index=3) 4600~5799 Module/Power Data of RS-485-1 (Index=4) 5800~6999 Module/Power Data of RS-485-1 (Index=5) 7000~8199 Module/Power Data of RS-485-1...
Page 256
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual 21000~22199 Module/Power Data of RS-485-2 (Index=1) 22200~23399 Module/Power Data of RS-485-2 (Index=2) 23400~24599 Module/Power Data of RS-485-2 (Index=3) 24600~25799 Module/Power Data of RS-485-2 (Index=4) 25800~26999 Module/Power Data of RS-485-2 (Index=5) 27000~28199 Module/Power Data of RS-485-2...
Page 257
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual 41000~42199 Module/Power Data of LAN (Index=1) 42200~43399 Module/Power Data of LAN (Index=2) 43400~44599 Module/Power Data of LAN (Index=3) 44600~45799 Module/Power Data of LAN (Index=4) 45800~46999 Module/Power Data of LAN (Index=5) 47000~48199 Module/Power Data of LAN...
Page 258
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual (1) PMC/PMD System Data This block stores the system information of PMC/PMD, shown as below: Modbus Data Parameter Name Length Range Address Type [1x] Discrete Input, Unit : Coil(8 Bits) 0=Disable Local FTP Server...
Page 259
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual Mobile Network Signal 300032 Int16 -32768~32767(dbm) Strength Mobile Network Signal 300033 Int16 0, 20, 40, 60, 80, 100 Strength (Percent) micro SD Free Space 300034 UInt16 0~65535(MB) -1=Initializing FTP Upload Status 300035 Int16 0=Failed...
Page 260
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual meter and Modbus TCP/RTU modules that are connected to the PMC/PMD. If the module is M-7000/DL/IR or power meter, it will show the module type. If it is the Modbus TCP/RTU module, it will show the Address or NetID of the module. Detailed...
Page 261
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual Internal Register 45 400148 Float Floating Point Internal Register 46 400150 Float Floating Point Internal Register 47 400152 Float Floating Point Internal Register 48 400154 Float Floating Point Internal Register 67 400192 Float Floating Point...
Page 262
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual DI Counter 0 300200 Uint32 0~4294967295 DI Counter 1 300202 UInt32 0~4294967295 DI Counter 2 300204 UInt32 0~4294967295 DI Counter 3 300206 UInt32 0~4294967295 DI Counter 4 300208 UInt32 0~4294967295 DI Counter 5 300210...
Page 263
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual DI Counter 7 300214 UInt32 0~4294967295 DI Counter 8 300216 UInt32 0~4294967295 DI Counter 9 300218 UInt32 0~4294967295 DI Counter 10 300220 UInt32 0~4294967295 DI Counter 11 300222 UInt32 0~4294967295 DI Counter 12 300224...
Page 264
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual DO Ch.2 000202 Byte 0=OFF, 1=ON DO Ch.3 000203 Byte 0=OFF, 1=ON DO Ch.4 000204 Byte 0=OFF, 1=ON DO Ch.5 000205 Byte 0=OFF, 1=ON Discrete Input (1x), Unit : Coil(8 Bits) DI Ch.0 100200...
Page 265
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual DI Counter 2 300212 UInt32 0~4294967295 DI Counter 3 300214 UInt32 0~4294967295 XV307 Modbus Data Parameter Name Length Range Address Type Coil Output (0x), Unit : Coil(8 Bits) DO Ch.0 000200 Byte 0=OFF, 1=ON DO Ch.1...
Page 266
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual Discrete Input (1x), Unit : Coil(8 Bits) DI Ch.0 100200 Byte 0=OFF, 1=ON DI Ch.1 100201 Byte 0=OFF, 1=ON DI Ch.2 100202 Byte 0=OFF, 1=ON DI Ch.3 100203 Byte 0=OFF, 1=ON DI Ch.4 100204...
Page 267
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual DI Ch.1 100201 Byte 0=OFF, 1=ON DI Ch.2 100202 Byte 0=OFF, 1=ON DI Ch.3 100203 Byte 0=OFF, 1=ON Input Register (3x), Unit : Register(16 Bits) AI Ch.0 300200 Float Floating Point AI Ch.1 300202...
Page 268
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual (7) Module Data This block stores all I/O channel data of M-7000/DL/IR modules, power data of power meters and I/O channel data of Modbus TCP/RTU modules. Depend on different configuration of I/O modules and power meters, the arrangement of data block will be different.
Page 269
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual M-7002 (5 DI、4 DO、4 AI channel) Data Parameter Name Modbus Address Length Range Type [0x] Coil Output, Unit : Coil(8 Bits) DO Ch.0 SA + 000000 Byte 0=OFF, 1=ON DO Ch.1 SA + 000001...
Page 270
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual [3x] Input Register, Unit : Register(16 Bits) AI Ch.0 SA + 300000 Float Floating Point AI Ch.1 SA + 300002 Float Floating Point AI Ch.2 SA + 300004 Float Floating Point AI Ch.3 SA + 300006...
Page 271
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual M-7016 (1 DI、4 DO、2 AI、1 AO channel) Data Parameter Name Modbus Address Length Range Type [0x] Coils Output, Unit : Coil(8 Bits) DO Ch.0 SA + 000000 Byte 0=OFF, 1=ON DO Ch.1 SA + 000001...
Page 272
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual M-7017Z (10 Differential AI channel) Data Parameter Name Modbus Address Length Range Type [3x] Input Register, Unit : Register(16 Bits) AI Ch.0 SA + 300000 Float Floating Point AI Ch.1 SA + 300002...
Page 273
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual AI Ch.16 SA + 300032 Float Floating Point AI Ch.17 SA + 300034 Float Floating Point AI Ch.18 SA + 300036 Float Floating Point AI Ch.19 SA + 300038 Float Floating Point M-7018Z、M-7019Z (10 AI channel)
Page 274
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual M-7024R (5 DI、4 AO channel) Data Parameter Name Modbus Address Length Range Type [1x] Discrete Input, Unit : Coil (8 Bits) DI Ch.0 SA + 100000 Byte 0=OFF, 1=ON DI Ch.1 SA + 100001...
Page 275
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual DO Ch.9 SA + 000009 Byte 0=OFF, 1=ON DO Ch.10 SA + 000010 Byte 0=OFF, 1=ON DO Ch.11 SA + 000011 Byte 0=OFF, 1=ON DO Ch.12 SA + 000012 Byte 0=OFF, 1=ON DO Ch.13...
Page 276
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual DI Counter 12 SA + 300012 UInt16 0~65535 DI Counter 13 SA + 300013 UInt16 0~65535 DI Counter 14 SA + 300014 UInt16 0~65535 DI Counter 15 SA + 300015 UInt16 0~65535 M-7080、M-7080B (2 Counter/Frequency、2 DO channel)
Page 277
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual PWM Output Ch.2 SA + 000002 Byte 0=OFF, 1=ON PWM Output Ch.3 SA + 000003 Byte 0=OFF, 1=ON PWM Output Ch.4 SA + 000004 Byte 0=OFF, 1=ON PWM Output Ch.5 SA + 000005 Byte 0=OFF, 1=ON PWM Output Ch.6...
Page 278
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual DL-302 (CO2、Temperature、Humidity、1 DO Channel) Modbus Data Parameter Name Length Range Address Type [0x] Coil Output, Unit : Coil(8 Bits) DO Ch.0 SA + 000000 Byte 0=OFF, 1=ON [3x] Input Register, Unit : Register(16 Bits)
Page 279
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual PM-2133 Modbus Data Parameter Name Length Range Address Type [3x] Input Register, Unit : Register(16 Bits) SA + 300000 Float Floating Point SA + 300002 Float Floating Point SA + 300004 Float Floating Point...
Page 280
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual SA + 300064 Float Floating Point SA + 300066 Float Floating Point kvarh SA + 300068 Float Floating Point kVAh SA + 300070 Float Floating Point 15/30/60 mins SA + 300072 Float Floating Point...
Page 281
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual Yearly Accumulated SA + 300102 Float Floating Point Electricity 15/30/60 mins SA + 300104 Float Floating Point Actual Demand 15/30/60 mins SA + 300106 Float Floating Point Forecast Demand Max. Demand SA + 300108...
Page 282
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual Yearly Accumulated SA + 300134 Float Floating Point Electricity [3x] Input Register, Unit : Register(16 Bits) Power Meter Type PM_SA + 300000 Int16 2133 Reserved PM_SA + 300001 Reserved Reserved PM_SA + 300002 Reserved...
Page 283
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual kvarh SA + 300032 Float Floating Point kVAh SA + 300034 Float Floating Point SA + 300036 Float Floating Point SA + 300038 Float Floating Point SA + 300040 Float Floating Point kvar SA + 300042...
Page 284
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual Accumulated Electricity 15/30/60 mins SA + 300088 Float Floating Point Actual Demand 15/30/60 mins SA + 300090 Float Floating Point Forecast Demand Max. Demand SA + 300092 Float Floating Point (Hourly) Max. Demand SA + 300094...
Page 285
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual Accumulated Electricity 15/30/60 mins SA + 300120 Float Floating Point Actual Demand 15/30/60 mins SA + 300122 Float Floating Point Forecast Demand Max. Demand SA + 300124 Float Floating Point (Hourly) Max. Demand SA + 300126...
Page 286
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual PM-3133、PM-3133-MTCP、PM-3033、PM-3033-MTCP Modbus Data Parameter Name Length Range Address Type [0x] Coils Output, Unit : Coil(8 Bits) (PM-3033/PM-3033-MTCP does not support this function.) DO Ch.0 SA + 000000 Byte 0=OFF, 1=ON DO Ch.1 SA + 000001...
Page 287
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual SA + 300046 Float Floating Point SA + 300048 Float Floating Point kvarh SA + 300050 Float Floating Point kVAh SA + 300052 Float Floating Point SA + 300054 Float Floating Point SA + 300056...
Page 288
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual Max. Demand SA + 300094 Float Floating Point (Daily) Max. Demand SA + 300096 Float Floating Point (Monthly) Daily Accumulated SA + 300098 Float Floating Point Electricity Monthly Accumulated SA + 300100 Float Floating Point...
Page 289
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual (Daily) Max. Demand SA + 300128 Float Floating Point (Monthly) Daily Accumulated SA + 300130 Float Floating Point Electricity Monthly Accumulated SA + 300132 Float Floating Point Electricity Yearly Accumulated SA + 300134 Float...
Page 290
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual PM-3112、PM-3112-MTCP (2 Loops 1 Phase) Modbus Data Parameter Name Length Range Address Type [0x] Coils Output, Unit : Coil(8 Bits) DO Ch.0 SA + 000000 Byte 0=OFF, 1=ON DO Ch.1 SA + 000001...
Page 291
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual Electricity Monthly Accumulated SA + 300048 Float Floating Point Electricity Yearly Accumulated SA + 300050 Float Floating Point Electricity 15/30/60 mins SA + 300052 Float Floating Point Actual Demand 15/30/60 mins SA + 300054...
Page 292
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual PM_SA + 300006 Int16 0~255 PM_SA + 300007 Int16 0~255 PM_SA + 300008 Int16 0~255 PM_SA + 300009 Int16 0~255 Port Number PM_SA + 300010 UInt16 1~65535 Reserved PM_SA + 300011 Reserved PT Ratio...
Page 293
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual SA + 300038 Float Floating Point SA + 300040 Float Floating Point kvar SA + 300042 Float Floating Point SA + 300044 Float Floating Point SA + 300046 Float Floating Point SA + 300048...
Page 294
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual 15/30/60 mins SA + 300090 Float Floating Point Forecast Demand Max. Demand SA + 300092 Float Floating Point (Hourly) Max. Demand SA + 300094 Float Floating Point (Daily) Max. Demand SA + 300096 Float...
Page 295
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual Forecast Demand Max. Demand SA + 300124 Float Floating Point (Hourly) Max. Demand SA + 300126 Float Floating Point (Daily) Max. Demand SA + 300128 Float Floating Point (Monthly) Daily Accumulated SA + 300130...
Page 296
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual PM-4324, PM-4324A, PM-4324-MTCP, PM-4324A-MTCP Modbus Data Parameter Name Length Range Address Type [0x] Coils Output, Unit : Coil(8 Bits) DO Ch.0 SA + 000000 Byte 0=OFF, 1=ON DO Ch.1 SA + 000001 Byte...
Page 297
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual 0: Disable Harmonic Selector 1: Phase A / CT19 SA + 400006 UInt16 [Submeter 7] 2: Phase B / CT20 3: Phase C / CT21 0: Disable 1: Phase A / CT22 Harmonic Selector...
Page 298
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual SA + 300054 Float Floating Point SA + 300056 Float Floating Point SA + 300058 Float Floating Point kvar SA + 300060 Float Floating Point SA + 300062 Float Floating Point SA + 300064...
Page 299
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual SA + 300126 Float Floating Point SA + 300128 Float Floating Point SA + 300130 Float Floating Point kvar SA + 300132 Float Floating Point SA + 300134 Float Floating Point SA + 300136...
Page 300
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual SA + 300198 Float Floating Point SA + 300200 Float Floating Point SA + 300202 Float Floating Point kvar SA + 300204 Float Floating Point SA + 300206 Float Floating Point SA + 300208...
Page 301
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual SA + 300270 Float Floating Point SA + 300272 Float Floating Point SA + 300274 Float Floating Point kvar SA + 300276 Float Floating Point SA + 300278 Float Floating Point SA + 300280...
Page 302
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual SA + 300342 Float Floating Point SA + 300344 Float Floating Point SA + 300346 Float Floating Point kvar SA + 300348 Float Floating Point SA + 300350 Float Floating Point SA + 300352...
Page 303
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual SA + 300414 Float Floating Point SA + 300416 Float Floating Point SA + 300418 Float Floating Point kvar SA + 300420 Float Floating Point SA + 300422 Float Floating Point SA + 300424...
Page 304
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual SA + 300486 Float Floating Point SA + 300488 Float Floating Point SA + 300490 Float Floating Point kvar SA + 300492 Float Floating Point SA + 300494 Float Floating Point SA + 300496...
Page 305
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual SA + 300558 Float Floating Point SA + 300560 Float Floating Point SA + 300562 Float Floating Point kvar SA + 300564 Float Floating Point SA + 300566 Float Floating Point SA + 300568...
Page 306
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual (Monthly) Daily Accumulated SA + 300602 Float Floating Point Electricity Monthly Accumulated SA + 300604 Float Floating Point Electricity Yearly Accumulated SA + 300606 Float Floating Point Electricity 15/30/60 mins SA + 300608 Float...
Page 307
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual (Monthly) Daily Accumulated SA + 300634 Float Floating Point Electricity Monthly Accumulated SA + 300636 Float Floating Point Electricity Yearly Accumulated SA + 300638 Float Floating Point Electricity Submeter 2 15/30/60 mins SA + 300640...
Page 308
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual (Monthly) Daily Accumulated SA + 300666 Float Floating Point Electricity Monthly Accumulated SA + 300668 Float Floating Point Electricity Yearly Accumulated SA + 300670 Float Floating Point Electricity 15/30/60 mins SA + 300672 Float...
Page 309
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual Daily Accumulated SA + 300698 Float Floating Point Electricity Monthly Accumulated SA + 300700 Float Floating Point Electricity Yearly Accumulated SA + 300702 Float Floating Point Electricity Submeter 3 15/30/60 mins SA + 300704...
Page 310
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual (Monthly) Daily Accumulated SA + 300730 Float Floating Point Electricity Monthly Accumulated SA + 300732 Float Floating Point Electricity Yearly Accumulated SA + 300734 Float Floating Point Electricity 15/30/60 mins SA + 300736 Float...
Page 311
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual (Monthly) Daily Accumulated SA + 300762 Float Floating Point Electricity Monthly Accumulated SA + 300764 Float Floating Point Electricity Yearly Accumulated SA + 300766 Float Floating Point Electricity Submeter 4 15/30/60 mins SA + 300768...
Page 312
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual (Monthly) Daily Accumulated SA + 300794 Float Floating Point Electricity Monthly Accumulated SA + 300796 Float Floating Point Electricity Yearly Accumulated SA + 300798 Float Floating Point Electricity 15/30/60 mins SA + 300800 Float...
Page 313
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual (Monthly) Daily Accumulated SA + 300826 Float Floating Point Electricity Monthly Accumulated SA + 300828 Float Floating Point Electricity Yearly Accumulated SA + 300830 Float Floating Point Electricity Submeter 5 15/30/60 mins SA + 300832...
Page 314
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual (Monthly) Daily Accumulated SA + 300858 Float Floating Point Electricity Monthly Accumulated SA + 300860 Float Floating Point Electricity Yearly Accumulated SA + 300862 Float Floating Point Electricity 15/30/60 mins SA + 300864 Float...
Page 315
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual (Monthly) Daily Accumulated SA + 300890 Float Floating Point Electricity Monthly Accumulated SA + 300892 Float Floating Point Electricity Yearly Accumulated SA + 300894 Float Floating Point Electricity Submeter 6 15/30/60 mins SA + 300896...
Page 316
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual (Monthly) Daily Accumulated SA + 300922 Float Floating Point Electricity Monthly Accumulated SA + 300924 Float Floating Point Electricity Yearly Accumulated SA + 300926 Float Floating Point Electricity 15/30/60 mins SA + 300928 Float...
Page 317
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual (Monthly) Daily Accumulated SA + 300954 Float Floating Point Electricity Monthly Accumulated SA + 300956 Float Floating Point Electricity Yearly Accumulated SA + 300958 Float Floating Point Electricity Submeter 7 15/30/60 mins SA + 300960...
Page 318
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual (Monthly) Daily Accumulated SA + 300986 Float Floating Point Electricity Monthly Accumulated SA + 300988 Float Floating Point Electricity Yearly Accumulated SA + 300990 Float Floating Point Electricity 15/30/60 mins SA + 300992 Float...
Page 319
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual (Monthly) Daily Accumulated SA + 301018 Float Floating Point Electricity Monthly Accumulated SA + 301020 Float Floating Point Electricity Yearly Accumulated SA + 301022 Float Floating Point Electricity Submeter 8 15/30/60 mins SA + 301024...
Page 320
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual (Monthly) Daily Accumulated SA + 301050 Float Floating Point Electricity Monthly Accumulated SA + 301052 Float Floating Point Electricity Yearly Accumulated SA + 301054 Float Floating Point Electricity 15/30/60 mins SA + 301056 Float...
Page 321
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual (Monthly) Daily Accumulated SA + 301082 Float Floating Point Electricity Monthly Accumulated SA + 301084 Float Floating Point Electricity Yearly Accumulated SA + 301086 Float Floating Point Electricity [3x] Input Register, Unit : Register(16 Bits)
Page 322
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual ITHD Submeter 8 SA + 301116 Float Floating Point VTHD Submeter 8 SA + 301118 Float Floating Point ITHD Frequency CT1/ SA + 301120 Float Floating Point Phase A Frequency CT2/ SA + 301122...
Page 323
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual Frequency CT15/ SA + 301156 Float Floating Point Phase C Frequency Maximum SA + 301158 Float Floating Point Frequency CT16/ SA + 301160 Float Floating Point Phase A Frequency CT17/ SA + 301162 Float...
Page 324
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual CT Ratio [3] PM_SA + 300018 Float 1~65535 CT Ratio [4] PM_SA + 300020 Float 1~65535 CT Ratio [5] PM_SA + 300022 Float 1~65535 CT Ratio [6] PM_SA + 300024 Float 1~65535 CT Ratio [7]...
Page 325
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual module is in sequence arrangement from the module starting address 3400. The detailed I/O channel information of the module: Modbus The Starting Address of Continuous Data Data Model Modbus RTU Module Number Coil Output...
Page 326
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual The allocation of the Modbus Address in PMC/PMD for the Discrete Input setting of this Modbus RTU module is shown as below: Discrete Input The Modbus Address in The mapping Modbus Index Modbus RTU Module...
Page 327
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual Appendix II:Reset to Factory Default Setting and Send Password to Administrator During the operation of PMC/PMD, if the hardware system setting data is lost or encounters any abnormal problem that you would like to reset the system to factory...
Page 328
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual 1. Power off the PMC/PMD. 2. Switch the Rotary Switch to position 7. 3. Power on the PMC/PMD, when the RUN/PWR LED Indicator turns to be Orange(ON state), it indicates that the setting is completed.
Page 329
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual Administrator password is "Admin". Guest password is "User". Local FTP password is "Admin". 3. Switch the Rotary Switch to position 0. Delete the data logger files and reset the accumulated values of the power meter.
Page 330
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual Appendix III:Setup the GTM-203M-3GWA with PMD Hardware installation 1. Install the SIM card and antenna on the GTM-203M-3GWA, and connect the device with Power(+10V ~ +30V Antenna SIM card GTM-203M-3GWA Power Supply 2. Connect the GTM-203M-3GWA and PMD by USB cable.
Page 331
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual Appendix IV:The configuration setting of M-7000/DL module PMC/PMD allows connection to ICP DAS M-7000/DL modules for the I/O channel data settings and data retrieve. However, for other configuration of the M-7000/DL modules must be completed via DCON Utility in advance, so that the PMC/PMD can accurately connect to M-7000/DL module.
Page 332
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual Start the DCON Utility and verify if the COM Port parameters are accurate.
Page 333
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual Perform “Search” to find all M-7000 modules that are connected to the PC. Click on the M-7000 module to bring up the “Configuration Window” and setup the parameters (such as Address, Baudrate) for the module. The “Configuration Window”...
Page 334
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual Communication Protocol: has to be set as Modbus RTU. Address: the address has to be set between 1~64, please note: the configuration of M-7000 module address on PMC/PMD has to be set exactly the same.
Page 335
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual Appendix V:The SNMP Variables for PMC/PMD The PMC/PMD provides SNMP (Simple Network Management Protocol) Agent to work with the SNMP Network Management software for monitoring the system data, power meter data and I/O module data. The following table lists the SNMP variables for the PMC/PMD.
Page 337
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual Private MIB File and SNMP Variables PMC/PMD provides the SNMP Agent can be used to monitor the system status, power meter status and I/O module status with the SNMP Network Management software. You can find the PMC/PMD SNMP MIB file on the Software CD or from the ICP DAS PMMS Web site.
Page 338
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual The SNMP Variables naming rule of the Power Meter connected with PMC. Every power meter that is connected to PMC-523x/PMC-224x provides the SNMP Variables as above (with its specific prefix denoted). The SNMP Variables naming rule of the power meters on Com3...
Page 339
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual com3io1DiscInputName com3io1DiscInputValue com3io1DiscInputModbusAdd com3io1DiscInputCounterValue com3io1DiscInputResetCounter com3io1CoilOutputIndex com3io1CoilOutputName com3io1CoilOutputValue com3io1CoilOutputModbusAdd com3io1CoilOutputAdvFunction com3io1InputRegIndex com3io1InputRegName com3io1InputRegValue com3io1InputRegModbusAdd com3io1InputRegType com3io1InputRegScaleRatio com3io1InputRegOffset com3io1InputRegDeadband com3io1InputRegScaleMin com3io1InputRegScaleMax com3io1HoldingRegIndex com3io1HoldingRegName com3io1HoldingRegValue com3io1HoldingRegModbusAdd com3io1HoldingRegType com3io1HoldingRegScaleRatio com3io1HoldingRegOffset com3io1HoldingRegDeadband The SNMP Variables naming rule of the I/O modules that are connected to PMC.
Page 340
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual PMD Series serialNumber firmwareVersion nickname systemCurrentTime webserverPort modbusTcpPort modbusTcpNetID microSDFreeSpace powerMeterAmount System ioModuleAmount demandInterval contractCapacity modemStatus registerStatus signal carbonEmissionsFactor com1pm1Index com1pm1Interface com1pm1ModbusID com1pm1Name com1pm1PTIndex com1pm1PTValue com1pm1CTIndex com1pm1CTValue com1pm1PollingTimeout com1pm1DOAmount com1pm1RetryInterval c com1pm1ScanRate com1pm1StatusCode com1pm1ChSubmeterIndex...
Page 341
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual prefix com2pm2 instead, and the Power Meter16 SNMP Variables are also similar to the listed information above but with prefix com2pm16 instead. The SNMP Variables naming rule of the power meters on LAN...
Page 342
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual The I/O Module1 SNMP Variables are similar as listed information above but with prefix com2io1, the I/O Module2 SNMP Variables are similar to listed information above but with prefix com2io2 instead, and the I/O Module16 SNMP Variables are also similar to the listed...
Page 343
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual Appendix VI:The format of CGI Query command PMC supports the HTTP protocol to retrieve the Power data value, I/O channel value, Internal Register value or system information. In addition, PMC also supports the JSON format for message exchange. JSON is a popular format; it can reduce the loading of data transfer, and is easy to be integrated with other Network system.
Page 344
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual In the CGI Query command, it consist two parameters: “job=get_ir_val” and “ir_no=1”. For “job=get_ir_val”, “job” is the name of the first parameter, “get_ir_val” is the value of the first parameter. The first parameter is used to query the value of Internal Register of PMC.
Page 345
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual Set up the I/O channel value. job=set_channel_val& Command if_type=val&com_port=val&module_no=val& ch_type=val&ch_addr=val&ch_value=val Name if_type Parameters Description The I/O module Interface Value 0: XV-Board 1: COM Port 2: Network Name com_port Description If the I/O interface is XV-Board or Ethernet, skip this parameter.
Page 346
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual channel sequence number starting from 0. For infrared module, the ch_addr is the output channels in binary format. The first bit (LSB) of the value represents the 1st channel. The 2th bit represents the 2th channel.
Page 347
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual Name if_type Parameters Description The type of I/O Interface Value 0: XV-Board 1: COM Port 2: Ethernet Name com_port Description If the I/O interface is XV-Board or Ethernet, skip this parameter. If the I/O interface is COM Port, it is for the COM Port number.
Page 349
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual to Phase A/ Phase B/ Phase C/ Total-Average channel. The channel is existed. Response "status": "OK", "result": { "value": 2.5, "connection": "ONLINE" //or "OFFLINE" The module or channel does not exist. "status": "CHANNEL_NOT_EXIST" Password error "status": "PASSWORD_INCORRECT"...
Page 350
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual …so on. Name module_no Description The index number of the module. Value Integer; start from 1. The module is existed. Response If it is a Modbus module: "status": "OK", "result": { "ci": [ "address": "32"...
Page 351
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual "ao": [4.5, 1.1, 2.2, …], "connection": "ONLINE" //or "OFFLINE" For power modules: "status": "OK", "result": { "v": [107.9,107.9,…], // list by channel "i": [42.5,0,…], "kw": [2.8,0,…], "kvar": [-3.5,0,…], "kva": [4.5,0,…], "pf": [0.63,0,…], "kwh": [26696.54,2000.93,…], "kvarh": [22803.2,24.7,…],...
Page 352
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual None Parameters Normal Response "status": "OK", "result": { "com2": [ "no": 1, "connection": "ONLINE" //or "OFFLINE" … "com3": [], //No modules or is in disabled status. "network": [ "no": 3, "connection": "OFFLINE" … Password error "status": "PASSWORD_INCORRECT"...
Page 353
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual The Internal Register is enabled. Response "status": "OK" The Internal Register is disabled. "status": "INTERNAL_REGISTER_NOT_EXIST" Password error "status": "PASSWORD_INCORRECT" Get the value of a specific Internal Register. job=get_ir_val& Command ir_no=val Name ir_no Parameters...
Page 354
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual Get the value of all Internal Registers which are enabled. job=get_irs_val Command None Parameters Normal Status Response "status": "OK", "result": [ "no": 1, "value": 100 … Password error "status": "PASSWORD_INCORRECT" Get the system time.
Page 355
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual Get the current free space of the micro SD card. job=get_sdcard_space Command None Parameters Normal Status Response "status": "OK", "result": { "free_space": 1560 //Free space. Unit is MB. No microSD card detected. "status": "SDCARD_NOT_EXIST"...
Page 356
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual Appendix VII:Change the value of output channel of module or Internal Register by MQTT protocol PMC/PMD supports the MQTT protocol. User can use it to change the value of the Internal Register of PMC/PMD or the value of the output channel of I/O module or power meter module which connect to PMC/PMD.
Page 357
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual The AO channel of ICP DAS I/O module Prefix/SET/interface/module_no/ao/channel_no Prefix Please refer to 9.3 MQTT Setting Topic interface com3, com4 or lan module_no 1~16 channel_no 0~15 Message Floating value The Coil Output channel of others I/O module...
Page 358
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual Appendix VIII:The JSON format for the communication with IoT Platform PMC/PMD supports the functions to publish the JSON format messages to Microsoft Azure and IBM Bluemix IoT Cloud platforms, and also subscribe/receive the JSON format messages from IoT Cloud platform to change the value of the output channel of I/O modules or power meter modules that are connected to PMC/PMD.
Page 359
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual "module_no" : The number indicates the order that the data of the power module or I/O module being stored in the PMC/PMD Modbus Table. The range is 1~16. If the connection interface is XV-Board, please ignore this field.
Page 360
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual holding_register Internal Register : It indicates the channel/loop/phase index, Modbus address or "ch_addr" Internal Register number. : It indicates the nickname of the channel/loop/phase. "nickname" "value" : It indicates the real-time value of the channel/loop/phase.
Page 361
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual The following is a format of the received message from IoT Cloud platform, it is used to change the value of DO channel 1 which resides at the PM-3112 power meter with module number 6 to ON. The power meter module is connected to the COM4 of PMC-5231.
Page 362
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual "msg_type":" CHANNEL_OUTPUT ", "if_type":1, "com_port":4, "module_no":3, "ch_type":"ao", "ch_addr":2, "nickname":"fan speed", "value":"5.0"...
Page 363
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual Appendix IX:PMC-523x / PMC-224x LED Indicators LED Status Modules Status PWR(Green) The module is powered on. The module is functioning RUN (Red) normally. The modem is not functioning, OFF and one flash per 2 seconds or no SIM card inside.
Page 364
4 WISE/PMC/PMD controllers connected and 1G database storage space". IoTstar supports WISE-523x/WISE-2x4x series (with v1.6.0 or later version firmware) and PMC-523x/PMC-2x4x/PMD series (with v3.6.0 or later version firmware). If the WISE/PMC/PMD does not install with the right firmware version. Please update the firmware.
Page 365
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual For the account application of “IoTstar Trial”, please refer to the following steps: i. Click “Enable” in the “Function Status” field of the “System Setting→Network Setting→IoTstar Connection Setting” on the PMC/PMD page to open the parameter setting page of “IoTstar Connection Setting”, then click the...
Page 366
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual Trial”, and then click the link of the account application of “IoTstar Trial” provided in the email to complete the activation process of the trial account iv. When the trial account is successfully activated, the page will display the “Successfully activated”...
Page 367
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual vi. Go back to the “IoTstar Connection Settings” page of PMC/PMD, and enter the “Username” and “Password” information you set in the step ii, click “Save” button to save the setting, then download the settings to PMC/PMD. After that, the PMC/PMD controller will connect to the “IoTstar Trial”...
Page 368
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual For more information about IoTstar IoT cloud management software, please refer to IoTstar official website.