Chapter 2: Specifications
C0-02DD2-D – 4 DC Input/4 Sourcing DC Output;
2 Analog In/2 Analog Out Micro PLC
PWR
RUN
ERR
PORT1
TX1
RX1
TX2
RX2
PORT2
RS-485
PORT3
TX3
RX3
WARNING: You must use proper software and firmware for this PLC unit.
Serial Number
Before 174018001
174018001 or later
You can find the serial number on the bottom of the product label.
NOTE: Please refer to the Analog I/O Configuration section in Chapter 3 for information on using the
analog I/O.
NOTE: There are no ZIPLink pre-wired PLC connection cables and modules for the Analog PLCs (cannot
mix discrete I/O and analog I/O signals in a ZIPLink cable).
2–54
CLICK PLC Hardware User Manual, 6th Edition, Rev. F – C0-USER-M
Wiring Diagram
C0-02DD2-D
C1
X1
X2
X3
X4
V1
L
Y1
L
Y2
L
Y3
L
Y4
C0
AD1V
AD1 I
AD2V
AD2 I
ACOM
DA1V
DA1 I
DA2V
DA2 I
Transmitter
P/S
Software
Firmware
V1.12 or later
V1.10 or later
V2.10 or later
V2.10 or later
24VDC
See Discrete I/O
Specifications - Inputs
(X1 through X4)
24
See Discrete I/O
VDC
Specifications - Outputs
(Y1 through Y4)
See Analog I/O Specifications -
Transmitter 0-5V
Voltage & Current Input
Transmitter 4-20mA
Transmitter 0-5V
(AD1V through AD2I)
Transmitter 4-20mA
See Analog I/O Specifications -
Voltage & Current Output (DA1V
through DA2I)
General Specifications
Current Consumption at 24VDC
Terminal Block Replacement Part No.
Weight
140mA
C0-16TB
5.3 oz (150g)
Need help?
Do you have a question about the C0-USER-M and is the answer not in the manual?