C0-08TA – 8-Point AC Output Module
8-pt 17-240 VAC triac output module, 2 commons, isolated, 0.3 A/pt, removable terminal
block included.
Wiring Diagram
C0-08TA
C0-08TA
PWR
PWR
17 - 240VAC
L
L
L
L
17 - 240VAC
L
L
L
L
N.C.
N.C. = Not Connected
Equivalent Output Circuit
Internal Module Circuitry
17-240 VAC
OUTPUT
L
*
COM
* Varistor Joule Rating: 20 J
Output Temperature Derating Chart
8
6
4
2
0
0
10
20
32
50
68
Surrounding Air Temperature (°C/°F)
*
Use every other output.
CLICK PLC Hardware User Manual, 6th Edition, Rev. F – C0-USER-M
17-240V 0.3A
17-240V 0.3A
V
V
Outputs per Module
50-60Hz
50-60Hz
Operating Voltage Range
Output Voltage Range
AC Frequency
Maximum Output Current
Minimum Load
Maximum Leakage Current
On Voltage Drop
C1
Maximum Inrush Current
1
2
OFF to ON Response
3
ON to OFF Response
4
Status Indicators
C2
5
Commons
6
Bus Power Required (24VDC)
7
8
Protection Circuit
Terminal Block Replacement
Weight
Optical Isolator
0.2 A/pt.
0.3 A/pt.
30
40
50
55 °C
85
104
122
131 °F
Chapter 2: Specifications
Output Specifications
8
17–240 VAC
13.5–288 VAC
47–63 Hz
0.3 A/point, 1.2 A/common
10mA
4mA @ 288 VAC
1.5 VAC @ > 0.1 A
3.0 VAC @ < 0.1 A
10A for 10ms
1ms
1ms + 1/2 cycle
Logic Side (8 points, red LED)
Power Indicator (green LED)
2 (4 points/common) Isolated
Max. 80mA (All Outputs On)
Not built into the module - Install protection
elements such as external fuse.
ADC p/n C0-8TB
3.5 oz (100g)
ZIPLink Pre-Wired PLC Connection
Cables and Modules for CLICK PLC
11-pin connector cable
ZL-C0-CBL11 (0.5 m length)
ZL-C0-CBL11-1 (1.0 m length)
ZL-C0-CBL11-2 (2.0 m length)
*
ZL-RTB20
20-pin feed-through
connector module
2–123