C0-4Ad2Da-2 - 4-Channel Analog Voltage Input And 2-Channel Analog Voltage Output Module - AutomationDirect C0-USER-M Manual

Table of Contents

Advertisement

Chapter 2: Specifications
C0-4AD2DA-2 – 4-Channel Analog Voltage Input and 2-Channel Analog
Voltage Output Module
4-channel analog voltage input (13-bit resolution) and 2-channel analog voltage output (12-bit
resolution) module, range: 0-10V.
terminal block included.
Wiring Diagram
Connect the unused input
channel to 0V terminal.
Voltage
Transmitter
Voltage
Transmitter
Voltage
Transmitter
Voltage
Transmitter
Ch1
Load
24VDC
Power
Ch2
Supply
Load
+
N.C. = Not Connected
NOTE: When using this module you must
also use CLICK programming software and
PLC firmware version V1.40 or later.
ZIPLink Pre-Wired PLC Connection
Cables and Modules for CLICK PLC
20-pin connector cable
ZL-C0-CBL20 (0.5 m length)
ZL-C0-CBL20-1 (1.0 m length)
ZL-C0-CBL20-2 (2.0 m length)
2–142
CLICK PLC Hardware User Manual, 6th Edition, Rev. F – C0-USER-M
CHn
C0-4AD2DA-2
C0-4AD2DA-2
0V
0-10V
0-10V
+
CH1
CH1
0V
0V
N.C.
+
CH2
CH2
0V
0V
N.C.
+
CH3
CH3
0V
0V
N.C.
+
CH4
CH4
0V
0V
N.C.
CH1
CH1
0V
0V
N.C.
CH2
CH2
0V
0V
N.C.
24V
24V
0V
0V
External 24VDC power required, removable
Field to Logic Side Isolation
All '0V'
All
terminals are
ter
External 24VDC Power
co
connected
Required
int
internally.
Base Power Required (24VDC)
Terminal Block Replacement
Weight
Inputs per Module
Input Range
Resolution
Input Type
Maximum Continuous Overload
Input Impedance
Filter Characteristics
Sample Duration Time
All Channel Update Rate
Open Circuit Detection Time
Conversion Method
Accuracy vs. Temperature
Maximum Inaccuracy
Linearity Error (End to End)
Input Stability and Repeatability
Full Scale Calibration Error
(including Offset)
Offset Calibration Error
Maximum Crosstalk at DC,
50/60 Hz
ZL-RTB20 20-pin feed-
through connector module
General Specifications
1800VAC for 1 sec.
65mA
20mA
ADC p/n C0-16TB
3.1 oz (86g)
Input Specifications
4
0–10 V
13-bit, 1.22 mV per count
Single ended (one common)
±100VDC
>150kΩ
Low pass, -3dB at 500Hz
5ms
20ms
Zero reading within 100ms
Successive approximation
±75 PPM/°C maximum
0.5% of range (including
temperature changes)
±3 count maximum,
monotonic with no missing
codes
±2 count maximum
±8 count maximum
±8 count maximum
±2 count maximum

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the C0-USER-M and is the answer not in the manual?

Subscribe to Our Youtube Channel

This manual is also suitable for:

C0-01ac