When input port 1 active or input port 2 active, if input port 3 is active, defined combination output is outputting; If input
port 3 inactive, defined combination output is not outputting;
When input port 1 inactive and input port 2 inactive, whatever input port 3 is active or not, defined combination output is
not outputting.

7.3 DEFINED CONTENTS OF DIGITAL INPUT PORTS

No.
Type
0
Users Configured
1
Reserved
2
Alarm Mute
3
Reset Alarm
4
60Hz Active
5
Lamp Test
6
Panel Lock
7
Redundancy Active
8
Idle Control Mode
9
Inhibit Auto Stop
10
Inhibit Auto Start
11
Inhibit Scheduled Start
12
Gen Close Inhibit
13
Gen Closed Input
14
Inhibit Gen Load
15
Reserved
16
Reserved
17
Auto Mode Lock
18
Auto Mode Invalid
19
Static Parallel Mode
20
Black Start Input
21
Inhibit Alarm Stop
22
Instrument Mode
23
Reserved
HGM9510N/HGM9530N Paralleled Genset Controller User Manual
Table 18 Defined Contents of Digital Input Ports
Users-defined alarm.
Active range:
Never: input inactive.
Always: input is active all the time.
From crank: detecting as soon as start.
From safety on: detecting after safety on run delay.
Can prohibit "Audible Alarm" output when input is active.
Can reset shutdown alarm and trip alarm when input is active.
Use for CANBUS engine and it is 60Hz when input is active.
All LED indicators are illuminating when input is active.
All buttons in panel is inactive except navigation buttons and there is
in the right top corner in LCD when input is active.
Not available for HGM9510N.
Under voltage/frequency/speed protection is inactive.
In Auto mode, during generator normal running, when input is active,
prohibit generator shutdown automatically.
In Auto mode, prohibit generator start automatically when input is
active.
In Auto mode, prohibit scheduled start genset when input is active.
When input is active and "Gen Close" needs to be output, "Gen Close"
process will wait and will not close genset.
Connect generator loading switch's auxiliary point.
Prohibit genset switch on when input is active.
When input is active, controller enters into Auto mode.
When input is active, controller won't work under Auto mode. Auto
key and simulate auto key input do not work.
All shutdown alarms are prohibited except emergence stop.(Means
battle mode)
All outputs are prohibited in this mode.
Description
Page 86 of 116