7.2.2

DEFINED PERIOD OUTPUT

Defined period output is composed by 2 parts, period output S1 and condition output S2.
While S1 and S2 are TRUE synchronously, OUTPUT;
While S1 or S2 is FALSE, NOT OUTPUT.
Period output S1 can set generator's one or more period output freely, can set the delayed time and
output time after enter into period.
Condition output S2 can set as any conditions in output ports.
NOTE: when delay time and output time both are 0 in period output S1, it is TRUE in this period.
For example:
Output period: start
Delay output time: 2s
Output time: 3s
Condition output contents: input port 1 is active
Close when condition output active/inactive: close when active (disconnect when inactive);
Input port 1 active, after enter "starts time" and delay 2s, this defined period output is outputting, after 3s, stop
outputting;
Input port 1 inactive, defined output period is not outputting.
7.2.3

DEFINED COMBINATION OUTPUT

Defined combination output is composed by 3 parts, or condition output S1, or condition output S2,
and condition output S3.
S1 or S2 is TRUE, and S3 is TRUE, defined combination output is outputting;
S1 and S2 are FALSE, or S3 is FALSE, defined combination output is not outputting.
NOTE: S1, S2, S3 can be set as any contents except for "defined combination output" in the output setting.
NOTE: 3 parts of defined combination output (S1, S2, S3) couldn't include or recursively include themselves.
For example:
Contents of or condition output S1: input port 1 is active;
Close when or condition output S1 is active/inactive: close when active (disconnect when inactive);
Contents of or condition output S2, input port 2 is active;
Close when or condition output S2 is active/inactive: close when active (disconnect when inactive);
Contents of and condition output S3: input port 3 is active;
Close when and condition output S3 is active/inactive: close when active (disconnect when inactive);