No.
Items
Flexible Sensor 2
1.
Setting
Digital Input Ports
Digital Input Port 1
1.
Contents Setting
2.
Active Type
Digital Input Port 2
1.
Contents Setting
2.
Active Type
Digital Input Port 3
1.
Contents Setting
2.
Active Type
Digital Input Port 4
1.
Contents Setting
2.
Active Type
Digital Input Port 5
1.
Contents Setting
2.
Active Type
3.
Active Range
4.
Active Actions
5.
Active Delay
6.
Description
Digital Input Port 6
1.
Contents Setting
2.
Active Type
Digital Input Port 7
1.
Contents Setting
2.
Active Type
3.
Active Range
4.
Active Actions
5.
Active Delay
6.
Description
HGM9510N/HGM9530N Paralleled Genset Controller User Manual
Parameters
Defaults
(0-1)
0
(0-70)
31
(0-1)
0
(0-70)
27
(0-1)
0
(0-70)
26
(0-1)
0
(0-70)
13
(0-1)
0
(0-70)
0
(0-1)
0
(0-3)
3
(0-7)
4
(0-20.0)s
2.0
(0-70)
44
(0-1)
0
(0-70)
0
(0-1)
0
(0-3)
3
(0-7)
4
(0-20.0)s
2.0
Description
0: Disable;
1: Enable;
Temperature/pressure/fuel level sensors
are optional.
Remote start (on demand).
0: Close 1: Open
Low oil pressure shutdown input
0: Close
1: Open
High temperature shutdown input
0: Close 1: Open
Gen close status input
0: Close 1: Open
Users-defined
0: Close
1: Open
0: From safety on 1: From starting
2: Always 3: Never
0: None; 1: Warning; 2: Block; 3: Safety Trip;
4: Safety Trip and Stop; 5: Trip; 6: Trip and
Stop; 7: Shutdown.
Time from detecting active to confirm
LCD displays detailed contents when the
input is active.
Master choice
0: Close 1: Open
Users-defined.
0: Close 1: Open
0: From safety on 1: From starting
2: Always 3: Never
0: None; 1: Warning; 2: Block; 3: Safety Trip;
4: Safety Trip and Stop; 5: Trip; 6: Trip and
Stop; 7: Shutdown.
Time from detecting active to confirm
LCD displays detailed contents when the
input is active.
Page 68 of 116