Smartgen HGM9510N User Manual page 56

Paralleled genset controller
Table of Contents

Advertisement

No.
Functions
12
Digi. input 1
13
Digi. input 2
14
Digi. input 3
15
Digi. input 4
16
Digi. input 5
17
Digi. input 6
18
Magnetic pickup shield
19
MP2
20
MP1
21
Digi. input 7
22
23
Digi. output 4
24
25
ECU TR
26
ECU CAN H
27
ECU CAN L
28
MSC(1) TR
29
MSC(1) CAN H
30
MSC(1) CAN L
31
GOV B(+)
32
GOV A(-)
33
AVR B(+)
34
AVR A(-)
35
RS485(1) TR
36
RS485(1) A(+)
37
RS485(1) B(-)
38
39
Digi. output 5
40
41
Digi. output 6
42
Bus A-phase voltage
43
input
Bus B-phase voltage
44
input
Bus C-phase voltage
45
input
46
Bus N-wire input
Genset A-phase voltage
47
input
Genset B-phase voltage
48
input
HGM9510N/HGM9530N Paralleled Genset Controller User Manual
Cable Size
1.0mm
2
Ground connected is active (B-).
1.0mm
2
Ground connected is active (B-).
2
1.0mm
Ground connected is active (B-).
1.0mm
2
Ground connected is active (B-).
1.0mm
2
Ground connected is active (B-).
1.0mm
2
Ground connected is active (B-).
Connect with speed sensor, and shielding line is
2
0.5mm
recommended. B- is already connected with speed
sensor input 2 in the inside controller.
1.0mm
2
Ground connected is active (B-).
Normally close output, rated 8A.
1.5mm
2
Public points of relay.
Normally open output, rated 8A.
/
Impedance-120Ω shielding wire is recommended, and
0.5mm
2
the single-end shall be earth connected. Short connect
TR with H and then connect to 120Ω terminal resistor.
0.5mm
2
/
Impedance-120Ω shielding wire is recommended, and
2
0.5mm
the single-end shall be earth connected. Short connect
0.5mm
2
TR with H and then connect to 120Ω terminal resistor.
0.5mm
2
Shielding wire is recommended. Shielding layer shall be
0.5mm
2
earth connected at GOV end.
0.5mm
2
Shielding wire is recommended. Shielding layer shall be
2
earth connected at AVR end.
0.5mm
/
Impedance-120Ω shielding wire is recommended, and
0.5mm
2
the single-end shall be earth connected. Short connect
TR with A(+) and then connect to 120Ω terminal resistor.
0.5mm
2
2
1.5mm
Normally close output, rated 8A.
1.5mm
2
Normally open output, rated 8A.
1.5mm
2
Public points of relay.
1.5mm
2
Normally open output, rated 8A.
1.5mm
2
Public points of relay.
1.0mm
2
Connect to A-phase of bus (2A fuse is recommended).
1.0mm
2
Connect to B-phase of bus (2A fuse is recommended).
1.0mm
2
Connect to C-phase of bus (2A fuse is recommended).
2
1.0mm
Connect to N-wire of bus.
Connect
1.0mm
2
recommended).
Connect
2
1.0mm
recommended).
Remark
to
A-phase
of
genset
to
B-phase
of
genset
(2A
fuse
is
(2A
fuse
is
Page 56 of 116

Advertisement

Table of Contents
loading

This manual is also suitable for:

Hgm9530n