Smartgen HGM9510N User Manual page 71

Paralleled genset controller
Table of Contents

Advertisement

No.
Items
4
AVR Output Type
5
AVR Reverse
6
AVR Action
Sync Check
1
Dead Bus Volt
2
Check Volt
3
Check Pos. Freq.
4
Check Neg. Freq.
5
Check Phase
6
Phase Angle Offset
7
Fail Sync Delay
8
Fail Sync Action
Multi Sync
Num. On MSC Bus
1.
MSC Fail Act
2.
MSC Baud Rate
3.
4.
Starting Option
Start All Time
5.
Balance Enable
6.
Balance Hours
7.
HGM9510N/HGM9530N Paralleled Genset Controller User Manual
Parameters
Defaults
(0-2)
2
(0-1)
0
(0-2)
1
(10-50)V
30
(0-30)V
3
(0-2.00)Hz
0.20
(0-2.00)Hz
0.10
(0-20)°
10
(0-360)°
0
(5.0-300.0) s
60.0
(0-7)
1
(1-32)
2
(0-7)
1
(0-3)
1
(0-1)
1
(0-3600)s
120
(0-1)
0
(1-1000)h
1
Description
Center Point
0: None 1: Internal Relays;
2: Internal Analogue
0: Disable;
1: Enable
0: None; 1: Adjust to Rated; 2: Adjust to
Center Point
It is considered Bus no power when Bus
voltage is lower than dead Bus voltage.
It is considered voltage synchronization
when the voltage difference between
Generator
and
Bus
synchronization voltage difference.
It is considered frequency synchronization
when the frequency difference between
Generator and Bus is less than "Check Pos.
Freq." but more than "Check Neg. Freq.".
It is considered "Check Phase" when the
initial phase difference is lower than
synchronization phase difference.
Gen initial phase will add pre-set phase
offset based on the sampling initial phase.
If sync signals are not detected during the
set "Fail Sync Delay", controller will initiate
corresponding alarms based on the "Fail
Sync Action".
It is the minimum MSC number.
0: None; 1: Warning; 2: Block; 3: Safety Trip;
4: Safety Trip and Stop; 5: Trip; 6: Trip and
Stop; 7: Shutdown.
0: 500kBit/s; 1: 250kBit/s;
2: 125kBit/s; 3: 50kBit/s.
0: Start All; 1: Start Sets on demand
When starting option is set as "start all",
controller will stop corresponding gensets
as required after "Start All Time" delay.
0: Disable;
1: Enable
When the input is active, the controller will
start/stop
the
genset
according to the running time and the
pre-set balanced running time.
is
lower
than
automatically
Page 71 of 116