Smartgen HGM9510N User Manual page 50

Paralleled genset controller
Table of Contents

Advertisement

No
Type
14
Over Power
15
Loss Excitation Fault
16
ECU Comm. Failure
17
ECU Alarm
18
Aux High Temp Alarm
19
Aux Low OP Alarm
20
MSC ID Error
21
Volt Bus Error
22
Gen Phase Seq Wrong
23
Bus Phase Seq Wrong
24
Temp. Sensor Open
25
Engine Temp High
26
Engine Temp Low
Oil Pressure Sensor
27
Open
HGM9510N/HGM9530N Paralleled Genset Controller User Manual
It is always detected.
When this is enabled, and the controller detects the genset power
(positive) is above the preset limit, it shall issue an alarm signal.
It is always detected.
When this is enabled, and the controller detects the genset reactive
power (negative) is above the preset limit, it shall issue an alarm signal.
It is always detected.
When the controller doesn't receive the engine alarm signal from
J1939, it shall issue an alarm signal.
It is always detected.
When the controller receives the engine alarm signal from J1939, it
shall issue an alarm signal.
It is always detected.
When the controller detects that this alarm in the input port is active, it
shall issue an alarm signal.
It is detected after "safety on time" before "ETS solenoid hold".
When the controller detects that this alarm in the input port is active, it
shall issue an alarm signal.
It is detected after "safety on time" before "ETS solenoid hold".
When the controller detects MSC bus has the same IDs, it shall issue
shutdown alarm signal.
It is always detected.
When the controller detects other genset are closed, but busbar voltage
is below the uncharged busbar voltage, it shall issue an alarm signal.
It is detected when gen is closed.
When the controller detects phase sequence error, it shall issue an
alarm signal.
It is always detected.
When the controller detects busbar sequence error, it shall issue an
alarm signal.
It is always detected.
When the controller detects the sensor circuit is open, it shall issue an
alarm signal.
It is always detected.
When this is enabled, and the controller detects the temp. is above the
preset limit, it shall issue an alarm signal.
It is detected after "safety on time" before "ETS solenoid hold".
When this is enabled, and the controller detects the temp. is below the
preset limit, it shall issue an alarm signal.
It is detected after "safety on time" before "ETS solenoid hold".
When the controller detects the sensor circuit is open, it shall issue an
alarm signal.
It is always detected.
Description
Page 50 of 116