Smartgen HGM9510N User Manual page 52

Paralleled genset controller
Table of Contents

Advertisement

No
Type
Charge Alternator
39
Failure
40
Battery Over Voltage
41
Battery Under Voltage
42
Fail to Sync.
43
MSC Too Few Sets
44
Maintenance Due
45
Low Coolant Level
46
Detonation Alarm
47
Gas Leakage Alarm
48
Digital Input Alarm
49
PLC Function Alarm
50
DIN16 Comm. Failure
51
DIN16 Input Alarm
HGM9510N/HGM9530N Paralleled Genset Controller User Manual
sensor is selected as temperature sensor and pressure sensor;
It is always detected when the sensor is selected as fuel level sensor.
When this is enabled, and the controller detects the charger voltage
value is below the preset limit, it shall issue an alarm signal.
It is detected when the genset is normally running.
When this is enabled, and the controller detects the battery voltage is
above the preset limit, it shall issue an alarm signal.
It is always detected.
When this is enabled, and the controller detects the battery voltage is
below the preset limit, it shall issue an alarm signal.
It is always detected.
If the controller doesn't detect sync. signal within the pre-set time, it will
initiate an alarm signal.
It is detected when closes.
When the controller detects the number of the paralleled gensets is
smaller than the set minimum paralleled number, it will initiate an alarm
signal. There are 2 possible reasons: a) the communication wire
between the controllers is detached, leading to communication
interrupt. b) the controller of paralleled gen-sets is not powered on.
It is always detected.
When this is enabled and countdown time is 0, it will initiate an alarm
signal.
It is detected when the genset is running.
When the controller detects Low Coolant Level in the input port is
active, it shall issue an alarm signal.
It is always detected.
When the controller detects Detonation Alarm in the input port is active,
it shall issue an alarm signal.
It is always detected.
When the controller detects Gas Leakage Alarm in the input port is
active, it shall issue an alarm signal.
It is always detected.
When the digital input port is set users-defined and if it is active, the
controller will initiate an alarm signal for the input port.
It is detected in the detection range set for the input port.
When PLC function is set users-defined and if it is active, the controller
will initiate an alarm signal.
It is detected in the detection range set by the PLC function.
When DIN16 communication is enabled and the controller cannot
receive the communication data, it will initiate an alarm signal.
It is always detected.
When DIN16 input is set users-defined and if it is active, the controller
will initiate an alarm signal.
Description
Page 52 of 116

Advertisement

Table of Contents
loading

This manual is also suitable for:

Hgm9530n