Defined Contents Of Configurable Input Ports (All Active When Connect To Ground (B-)) - Smartgen HGM8110DC-2 User Manual

Genset controller
Table of Contents

Advertisement

8.3 DEFINED CONTENTS OF CONFIGURABLE INPUT PORTS (All Active when connect to
Ground (B-))
No.
0
Users Configured
1
Reserved
2
Alarm Mute
3
Reset Alarm
4
60Hz Active
5
Lamp Test
6
Panel Lock
7
War Mode
8
Idle Mode
9
Auto Stop Inhibit
10
Auto Start Inhibit
11
Scheduled Run Inhibit
12
Reserved
13
Generator Close Status
14
Generator Load Inhibit
15
Reserved
16
Reserved
17
Auto Mode Lock
18
Auto Mode Inhibit
19
Reserved
20
Reserved
HGM8110DC-2 Genset Controller
HGM8110DC-2 GENSET CONTROLLER USER MANUAL
Table 15 - Defined Contents of Programmable Inputs
Type
Including following functions,
Indication: indicate only, not warning or shutdown.
Warning: warn only, not shutdown.
Shutdown: alarm and shutdown immediately
Trip and stop: alarm, generator unloads and shutdown after
hi-speed cooling
Trip: alarm, generator unloads but not shutdown.
Never: input inactive.
Always: input is active all the time.
From crank: detecting as soon as start.
From safety on: detecting after safety on run delay.
Can prohibit ―Audible Alarm‖ output when input is active.
Can reset shutdown alarm and trip alarm when input is active.
Use for CANBUS engine and it is 60Hz when input is active.
All LED indicators are illuminated when input is active.
All buttons in panel are inactive except navigation and exit
buttons and there is
input is active.
All shutdown alarms except alarms of emergency stop and
over speed shutdown cannot stop the engine in the war
mode.
Under voltage/frequency/speed protection is inactive.
In Auto mode, during generator normal running, when input
is active, inhibit generator shutdown automatically.
In Auto mode, inhibit generator start automatically when input
is active.
In Auto mode, inhibit scheduled run genset when input is
active.
Connect generator loading switch's Aux. Point.
Prohibit genset switch on when input is active.
When input is active, controller enters into auto mode; mode
selection buttons are inactive.
When input is active, controller won't work under auto mode.
Auto mode key and simulate auto key input does not work.
2020-02-20
Description
on the right of first row in LCD when
Version 1.0
Page 50 of 69