Smartgen HGM9510N User Manual page 27

Paralleled genset controller
Table of Contents

Advertisement

No
Type
26
Flex. Sensor 1 Wrong
27
Flex. Sensor 2 Open
28
Flex. Sensor 2 High
29
Flex. Sensor 2 Low
Charge Alternator
30
Failure
31
Battery Over Voltage
32
Battery Under Voltage
33
Fail to Sync.
34
MSC Too Few Sets
35
Maintenance Due
36
Digital Input Alarm
HGM9510N/HGM9530N Paralleled Genset Controller User Manual
It is always detected when the sensor is selected as fuel level sensor.
When voltage or current input is selected for the curve type of the
controller, and the controller detects input signal is abnormal, it shall
issue a block alarm, and meanwhile the curve is transferred to resistor
type to prevent damaging the controller.
It is always detected.
When the controller detects the sensor circuit is open, it shall issue a
block alarm.
It is always detected.
When over high block alarm is enabled, and the controller detects the
sensor value is above the preset upper limit, it shall issue a block alarm.
It is detected after "safety on time" before "ETS solenoid hold" when the
sensor is selected as temperature sensor and pressure sensor;
It is always detected when the sensor is selected as fuel level sensor.
When over low block alarm is enabled, and the controller detects the
sensor value is below the preset low limit, it shall issue a block alarm.
It is detected after "safety on time" before "ETS solenoid hold" when the
sensor is selected as temperature sensor and pressure sensor;
It is always detected when the sensor is selected as fuel level sensor.
When this is enabled, and the controller detects the charger voltage
value is below the preset limit, it shall issue a block alarm.
It is detected when the genset is normally running.
When this is enabled, and the controller detects the battery voltage is
above the preset limit, it shall issue a block signal.
It is always detected.
When this is enabled, and the controller detects the battery voltage is
below the preset limit, it shall issue a block signal.
It is always detected.
If the controller doesn't detect sync. signal within the pre-set time, it will
initiate a block alarm.
It is detected when breaker closes.
When the controller detects the number of the paralleled gensets is
smaller than the set minimum paralleled number, it will initiate a block
alarm. There are 2 possible reasons: a) the communication wire
between the controllers is detached, leading to communication
interrupt. b) the controller of paralleled gensets is not powered on.
It is always detected.
When this is enabled and countdown time is 0, it will initiate a block
alarm.
It is detected when the genset is running.
When the digital input port is set users-defined and if it is active, the
controller will initiate a block signal for the input port.
It is detected in the detection range set for the input port.
Description
Page 27 of 116

Advertisement

Table of Contents
loading

This manual is also suitable for:

Hgm9530n

Table of Contents