22.11 MTU ADEC (SMART MODULE)
Suitable for MTU engines with ADEC (ECU8) and SMART module.
Terminals of controller
Fuel relay output
Starting relay output
Terminals of controller
CAN GND
CAN(H)
CAN(L)
Engine type: MTU-ADEC.
22.12 MTU ADEC (SAM MODULE)
It is suitable for MTU engine with ADEC (ECU7) and SAM module.
Terminals of controller
Fuel relay output
Starting relay output
Terminals of controller
CAN GND
CAN(H)
CAN(L)
Engine type: Common J1939.
22.13 PERKINS
It is suitable for ADEM3/ADEM4 engine control module. Engine type is 2306, 2506, 1106, and 2806.
HGM9510N/HGM9530N Paralleled Genset Controller User Manual
Table 36 ADEC
ADEC (X1 port)
X1 10
X1 34
Table 37 SMART
SMART (X4 port)
X4 3
X4 1
X4 2
Table 38 ADEC
ADEC (X1 port)
X1 43
X1 37
Table 39 SAM
SAM (X23 port)
X23 3
X23 2
X23 1
Remark
X1 9 shall connect battery negative.
X1 33 shall connect battery negative.
Remark
CAN communication shielding line (connected
with controller's this terminal only).
Using impedance 120Ω connecting line.
Using impedance 120Ω connecting line.
Remark
X1 28 shall connect negative of battery.
X1 22 shall connect negative of battery.
Remark
CAN communication shielding line (connected
with controller's this terminal only).
Using impedance 120Ω connecting line.
Using impedance 120Ω connecting line.
Page 112 of 116