Micro SD card NOTE: (1) Two of the outputs are fixed: start output and fuel output. (2)HGM9510’s analog sensors are composed by 3 fixed sensors (temperature, pressure, level) and 2 configurable sensors. NOTE: The features of HGM9210/HGM9220/HGM9310/HGM9320/HGM9410/ HGM9420/HGM9520/HGM9610/HGM9620 controllers mentioned in this document may change, please check the corresponding user manual for accurate information.
HGM9510 GENSET PARALLEL UNIT 5 OPERATION INDICATOR LIGHT NOTE: Selected light indicators description: Warning indicator and Alarm indicator: Alarm Type Warning Indicator Alarm Indicator Warning Slow flashing Slow flashing Trip Alarm Slow flashing Slow flashing Shutdown Alarm Fast flashing Trip and Stop Alarm Fast flashing Running indicator: illuminated from crank disconnect to ETS while off during other periods.
HGM9510 GENSET PARALLEL UNIT 5.2 PUSHBUTTONS Icon Button Description Stop running generator in Auto/Manual mode; Lamp test (press at least 3 seconds); Reset alarm in stop mode; Stop During stopping process, press this button again to stop generator immediately. Start Start genset in Manual mode.
HGM9510 GENSET PARALLEL UNIT 7 WIRING CONNECTION HGM9510 controller’s rear as following: Description of terminal connection: Cable Functions Remark Size 2.5mm Connected with negative of starter battery. Connected with positive of starter battery. If wire 2.5mm length is over 30m, better to double wires in parallel.
Page 6
Battery Voltage Input NOTE: HGM9510 controller can suit for widely range of battery voltage (8~35) VDC. Negative of battery must be connected with the shell of starter stable. The wire’s diameter must be over 2.5mm...