Defined Contents Of Programmable Input Ports (All Gnd (B-) Active) - Smartgen HGM8151 User Manual

Genset parallel controller
Table of Contents

Advertisement

When input port 1 inactive and input port 2 inactive, whatever input port 3 is active or not, Defined combination output is
not outputting.
7.3

DEFINED CONTENTS OF PROGRAMMABLE INPUT PORTS (ALL GND (B-) ACTIVE)

No.
Type
0
Users Configured
1
Reserved
2
Alarm Mute
3
Alarm Reset
4
60Hz Active
5
Lamp Test
6
Panel Lock
7
Reserved
8
Idle Speed Active
9
Auto Stop Inhibit
10
Auto Start Inhibit
11
Scheduled Run Inhibit
12
Reserved
13
Gen Closed Auxiliary
14
Gen Load Inhibit
15
Reserved
16
Reserved
17
Auto Mode Lock
18
Auto Mode Inhibit
19
Static Parallel
HGM8151 Genset Parallel Controller User Manual
Table 14 Defined Contents of Programmable Input Ports
Including following functions,
Indication: indicate only, not warning or shutdown.
Warning: warn only, not shutdown.
Shutdown: alarm and shutdown immediately
Trip and stop: alarm, generator unloads and shutdown after
hi-speed cooling
Trip: alarm, generator unloads but not shutdown.
Never: input inactive.
Always: input is active all the time.
From crank: detecting as soon as start.
From safety on: detecting after safety on run delay.
Can prohibit "Audible Alarm" output when input is active.
Can reset shutdown alarm and trip alarm when input is active.
Use for CANBUS engine and it is 60Hz when input is active.
All LED indicators are illuminating when input is active.
All buttons in panel is inactive except
there is
Under voltage/frequency/speed protection is inactive.
In Auto mode, during generator normal running, when input is
active, prohibit generator shutdown automatically.
In Auto mode, prohibit generator start automatically when input is
active.
In Auto mode, prohibit fixed timing start genset when input is
active.
Connect generator loading switch's Aux. Point.
Prohibit genset switch on when input is active.
When input is active, controller enters Auto mode; mode selection
keys in the panel are inactive.
When input is active, controller won't work under Auto mode key
and simulate auto key input does not work.
Description
in the right of first row in LCD when input is active.
and
Page 40 of 66

Advertisement

Table of Contents
loading

Table of Contents