Smartgen HGM9510N User Manual page 23

Paralleled genset controller
Table of Contents

Advertisement

No
Type
50
PLC Function Alarm
51
DIN16 Comm. Failure
52
DIN16 Input Alarm
DOUT16
53
Failure
54
AIN24 Comm. Failure
AIN24 Cylinder Temp.
55
High
AIN24 Exhaust Temp.
56
High
AIN24 Cylinder Temp.
57
Difference High
58
AIN24 Sensor Open
59
AIN24 Sensor High
60
AIN24 Sensor Low
61
Power Factor Low
HGM9510N/HGM9530N Paralleled Genset Controller User Manual
controller will initiate a warning for the input port.
It is detected in the detection range set for the input port.
When PLC function is set users-defined and if it is active, the controller
will initiate a warning.
It is detected in the detection range set by the PLC function.
When DIN16 communication is enabled and the controller cannot
receive the communication data, it will initiate a warning.
It is always detected.
When DIN16 input is set users-defined and if it is active, the controller
will initiate a warning.
It is detected in the detection range set in the input.
When DOUT16 communication is enabled and the controller cannot
Comm.
receive the communication data, it will initiate a warning.
It is always detected.
When AIN24 communication is enabled and the controller cannot
receive the communication data, it will initiate a warning.
It is always detected.
When this is enabled and the controller detects cylinder temperature
has exceeded the pre-set value, it will initiate a warning alarm.
It is detected after "safety on time" before "ETS solenoid hold".
When this is enabled and the controller detects exhaust temperature
has exceeded the pre-set value, it will initiate a warning alarm.
It is detected after "safety on time" before "ETS solenoid hold".
When this is enabled and the controller detects cylinder temp.
difference has exceeded the pre-set value, it will initiate a warning
alarm.
It is detected after "safety on time" before "ETS solenoid hold".
When the controller detects the sensor circuit is open, it shall issue a
warning.
It is always detected.
When over high warning is enabled, and the controller detects the
sensor value is above the preset upper limit, it shall issue a warning.
It is detected after "safety on time" before "ETS solenoid hold" when the
sensor is selected as temperature sensor and pressure sensor;
It is always detected when the sensor is selected as fuel level sensor.
When over low warning is enabled, and the controller detects the
sensor value is below the preset lower limit, it shall issue a warning.
It is detected after "safety on time" before "ETS solenoid hold" when the
sensor is selected as temperature sensor and pressure sensor;
It is always detected when the sensor is selected as fuel level sensor.
When this is enabled and the controller detects that the generator
power factor has fallen below the pre-set value, it will initiate a warning
alarm.
Description
Page 23 of 116