Defined Contents Of Configurable Input Ports (All Gnd(B-) Connected Active) - Smartgen GENSET HGM8100N Series User Manual

Genset controller
Table of Contents

Advertisement

8.3

DEFINED CONTENTS OF CONFIGURABLE INPUT PORTS (ALL GND(B-) CONNECTED ACTIVE)

No.
0
Users Defined
1
Reserved
2
Alarm Mute
3
Reset Alarm
4
60Hz Active
5
Lamp Test
6
Panel Lock
7
Reserved
8
Idle Speed Active
9
Auto Stop Inhibit
10
Auto Start Inhibit
11
Scheduled Run Inhibit
12
Reserved
13
Gen Closed Auxiliary
14
Gen Load Inhibit
15
Mains Closed Auxiliary
16
Mains Load Inhibit
17
Auto Mode Lock
18
Auto Mode Inhibit
19
Reserved
20
Reserved
HGM8100N Genset Controller User Manual
Table 15 Defined Contents of Configurable Input Ports
Type
Including following functions,
Indication: indicate only, not warning or shutdown.
Warning: warn only, not shutdown.
Shutdown: alarm and shutdown immediately
Trip and stop: alarm, generator unloads and shuts down
after hi-speed cooling
Trip: alarm, generator unloads but not shutdown.
Never: input inactive.
Always: input is active all the time.
From crank: detecting as soon as start.
From safety on: detecting after safety on run delay.
Can prohibit "Audible Alarm" output when input is active.
Can reset shutdown alarm and trip alarm when input is
active.
Use for CANBUS engine and it is 60Hz when input is
active.
All LED indicators are illuminating when input is active.
All buttons in panel is inactive except direction buttons
and there is
is active.
Under voltage/frequency/speed protection is inactive.
In Auto mode, during generator normal running, when
input is active, inhibit generator shutdown automatically.
In Auto mode, inhibit generator start automatically when
input is active.
In Auto mode, inhibit scheduled run genset when input is
active.
Connect generator loading switch's Aux. Point.
Prohibit genset switch on when input is active.
Connect mains loading switch's Aux. Point.
Prohibit mains switch on when input is active.
When input is active, controller enters into Auto mode;
mode selection buttons are inactive.
When input is active, controller won't work under Auto
mode. Auto mode key and simulate auto key input does
not work.
Description
in the right of first row in LCD when input
Page 43 of 66

Advertisement

Table of Contents
loading