8.3 DEFINED CONTENTS OF PROGRAMMABLE INPUT PORTS (ALL ACTIVE WHEN CONNECT TO GRAND
(B~))
No.
0
Users Configured
1
Reserved
2
Alarm Mute
3
Reset Alarm
4
Reserved
5
Lamp Test
6
Panel Lock
7~8
Reserved
9
Inhibit Auto Stop
10
Inhibit Auto Start
11
Inhibit Scheduled Start
12
Reserved
13
Aux Bus Closed
14
Inhibit Bus Load
15
Aux Mains Closed
16
Inhibit Mains Load
17
Auto Mode Lock
18
Auto Mode Invalid
19
Reserved
20
Reserved
21
Inhibit Alarm Stop
22
Aux Instrument Mode
23
Reserved
HGM9560 Bus Tie Mains Parallel Unit
Table 14 Definable Contents of Programmable Input Ports
Type
Including following functions,
Indication: indicate only, not warning or shutdown.
Warning: warn only, not shutdown.
Trip and stop: alarm, generator unloads and shutdown after
hi-speed cooling
Trip: alarm, generator unloads but not shutdown.
Mains Trip: alarm, mains opening outputs.
Never: input inactive.
Always: input is active all the time.
From paralleling: detect when the genset is parallel running.
Can prohibit "Audible Alarm" output when input is active.
Can reset shutdown alarm and trip alarm when input is active.
All LED indicators are illuminating when input is active.
All buttons in panel is inactive except
there is
In Auto mode, during generator normal running, when input is
active, prohibit generator shutdown automatically.
In Auto mode, prohibit generator start automatically when input
is active.
In Auto mode, prohibit fixed timing start genset when input is
active.
Connect bus loading switch's Aux. Point.
Prohibit bus switch on when input is active.
Connect mains loading switch's Aux. Point.
Prohibit mains switch on when input is active.
When input is active, controller enters into Auto mode; all the
keys except
When input is active, controller won't work under Auto mode.
All shutdown alarms are prohibited except emergence
stop.(Means battle mode)
All outputs are prohibited in this mode.
Description
in the right of first row in LCD when input is active.
key and simulate auto key input does not work.
and
are inactive.