Defined Contents Of Programmable Input Ports (All Gnd(B-) Connected Active) - Smartgen HGM9510 User Manual

Genset parallel (with genset) controller
Hide thumbs Also See for HGM9510:
Table of Contents

Advertisement

Close when OR condition output S2 is active /inactive: close when active (disconnect when inactive);
Contents of AND condition output S3: output port 3 is active;
Close when AND condition output S3 is active /inactive: close when active (disconnect when inactive);
When input port 1 active or input port 2 active, if input port 3 is active, defined combination output is outputting; If input port 3
inactive, defined combination output is not outputting;
When input port 1 inactive and input port 2 inactive, whatever input port 3 is active or not, defined combination output is not
outputting.

8.3 DEFINED CONTENTS OF PROGRAMMABLE INPUT PORTS (ALL GND(B-) CONNECTED ACTIVE)

Table 15 Defined Contents of Programmable Input Ports (All GND(B-) Connected Active)
No.
0
Users Configured
1
Reserved
2
Alarm Mute
3
Reset Alarm
4
60Hz Select
5
Lamp Test
6
Panel Lock
7
Reserved
8
Idle Control Mode
9
Inhibit Auto Stop
10
Inhibit Auto Start
11
Inhibit Scheduled
12
Reserved
13
Aux Gen Closed
14
Inhibit Gen Load
15
Reserved
HGM9510 Genset Parallel Controller User Manual
Type
Including following functions,
Indication: indicate only, not warning or shutdown.
Warning: warn only, not shutdown.
Shutdown: alarm and shutdown immediately
Trip and stop: alarm, generator unloads and shuts down after
high-speed cooling
Trip: alarm, generator unloads but not shutdown.
Never: input inactive.
Always: input is active all the time.
From crank: detecting as soon as start.
From safety on: detecting after safety on run delay.
Can prohibit "Audible Alarm" output when input is active.
Can reset shutdown alarm and trip alarm when input is active.
Use for ECU engine with CANBUS and it is 60Hz when input is
active.
All LED indicators are illuminating when input is active.
All buttons in panel is inactive except
there is
Under voltage/frequency/speed protection is inactive.
In Auto mode, during generator normal running, when input is
active, prohibit generator shutdown automatically.
In Auto mode, prohibit generator start automatically when input
is active.
In Auto mode, prohibit scheduled start genset when input is
active.
Connect generator loading switch's Aux. Point.
Prohibit genset switch on when input is active.
Description
in the right of first row in LCD when input is active.
and
Page 45 of 68