Parameter
Fuel Output
Crank Output
Digital Output 1
Digital Output 2
Digital Output 3
Digital Output 4
Digital Output 5
Digital Output 6
Digital Output 7
Digital Output 8
Digital Input 1-10
RS485
Ethernet
MSC CAN
EMC/CE Certification
Vibration Test
Shock Test
Bump Test
Safety Requirements
Case Dimensions
HGM9510N/HGM9530N Paralleled Genset Controller User Manual
16A DC24V DC power supply output (relay output)
3A DC12V/30V power supply output (relay output) (UL certified
product)
16A DC24V DC power supply output (relay output)
3A DC12V/30V power supply output (relay output) (UL certified
product)
8A DC30V power supply output (relay output)
5A DC24V power supply output (relay output) (UL certified product)
8A DC30V power supply output (relay output)
5A DC24V power supply output (relay output) (UL certified product)
8A DC30V power supply output (relay output)
5A DC24V power supply output (relay output) (UL certified product)
8A AC250V volt-free output (relay output)
5A AC250V volt-free output (relay output) (UL certified product)
8A AC250V volt-free output (relay output)
5A AC150V volt-free output (relay output) (UL certified product)
8A AC250V volt-free output (relay output)
5A AC150V volt-free output (relay output) (UL certified product)
1A DC30V power supply output (transistor output)
1A DC30V/12V power supply output (transistor output) (UL certified
product)
1A DC30V power supply output (transistor output)
1A DC30V/12V power supply output (transistor output) (UL certified
product)
Low limit voltage is 1.2V, high limit voltage is 60V
Isolated, half-duplex, 9600 baud rate, maximum communication
length 1000m
Self-adapting 10/100Mbit
Isolated, maximum communication length 250m; applying Belden
9841 cable or the equivalence;
EN 61326-1:2013
5 - 8 Hz: ±7.5 mm
8 - 500 Hz: 2g
IEC 60068-2-6
50g, 11ms, half-sine, complete shock test from three directions, and
18 times shock for each test
IEC 60068-2-27
25g, 16ms, half-sine
IEC 60255-21-2
According to EN 61010-1 installation category (over voltage category)
III,
300V, pollution class 2, altitude 3000m
242mm x 186mm x 49mm