User Menu And Parameter Setting - Smartgen HGM9510N User Manual

Paralleled genset controller
Table of Contents

Advertisement

Power
Conditions
Factor
COS>0L
P>0,Q>0
COS>0C
P>0,Q<0
COS<0L
P<0,Q>0
COS<0C
P<0,Q<0
NOTES:
1.
Input active power, and generator sends electricity to load.
2.
Output active power, and load supplies electricity to generator.
3.
Input reactive power, and generator sends reactive power to load.
4.
Output reactive power, and load sends reactive power to generator.
Bus page includes the following contents:
Phase voltage, wire voltage, frequency, phase sequence; available power.
Sync. page includes the following contents:
Voltage difference, frequency difference, phase difference, active power output and target percentage,
reactive power output and target percentage, GOV voltage output percentage, AVR voltage output
percentage and MSC status.
Alarm page:
Current alarm information.
NOTE: For ECU alarms and shutdown alarms, if the alarm information is displayed, check the engine according to it.
Otherwise, please check the engine manual according to SPN alarm code.
Event log page:
Make records about all start/stop events (alarm events except warnings, manual start/stop events) and
the real time when events occur;
Others page includes the following contents:
Time and date, maintenance countdown (if configured), input/output port status, communication
indication and Ethernet configuration (if configured).
About page includes the following contents:
Release software version, hardware version, and product PD number.
4.3.2

USER MENU AND PARAMETER SETTING

Press
key for more than 1s and it enters user menu.
Parameter Setting
After inputting the correct password (factory default password is 00318) you can enter the parameter
setting screen.
Language
Optional Simplified Chinese, English and others.
Commissioning
On load, off load and users-defined commissioning are optional. Defined commissioning can be
configured regarding load on or load off, commissioning time, and which mode it shall return after
commissioning (manual mode, auto mode and stop mode).
HGM9510N/HGM9530N Paralleled Genset Controller User Manual
Table 6 Power Factor Display Description
Active
Reactive
Power
Power
Input
Input
Input
Output
Output
Input
Output
Output
Remark
Load is resistive induction.
Load is resistive capacitance.
Load equals an under excitation generator.
Load equals an over excitation generator.
Page 15 of 116