No.
Items
Digital Input Port 8
1.
Contents Setting
2.
Active Type
3.
Active Range
4.
Active Actions
5.
Active Delay
6.
Description
Digital Input Port 9
1.
Contents Setting
2.
Active Type
3.
Active Range
4.
Active Actions
5.
Active Delay
6.
Description
Digital Input Port 10
1.
Contents Setting
2.
Active Type
3.
Active Range
4.
Active Actions
5.
Active Delay
6.
Description
Digital Output Ports
Digital Output Port 1
1
Contents Setting
2
Active Type
Digital Output Port 2
1
Contents Setting
2
Active Type
Digital Output Port 3
1
Contents Setting
HGM9510N/HGM9530N Paralleled Genset Controller User Manual
Parameters
Defaults
(0-70)
0
(0-1)
0
(0-3)
3
(0-7)
4
(0-20.0)s
2.0
(0-70)
0
(0-1)
0
(0-3)
3
(0-7)
4
(0-20.0)s
2.0
(0-70)
0
(0-1)
0
(0-3)
3
(0-7)
4
(0-20.0)s
2.0
(0-299)
44
(0-1)
0
(0-299)
48
(0-1)
0
(0-299)
38
Description
User defined.
0: Close
1: Open
0: From safety on 1: From starting
2: Always 3: Never
0: None; 1: Warning; 2: Block; 3: Safety Trip;
4: Safety Trip and Stop; 5: Trip; 6: Trip and
Stop; 7: Shutdown.
Time from detecting active to confirm
LCD displays detailed contents when the
input is active.
Users-defined
0: Close
1: Open
0: From safety on 1: From starting
2: Always 3: Never
0: None; 1: Warning; 2: Block; 3: Safety Trip;
4: Safety Trip and Stop; 5: Trip; 6: Trip and
Stop; 7: Shutdown.
Time from detecting active to confirm
LCD displays detailed contents when the
input is active.
Users-defined
0: Close
1: Open
0: From safety on 1: From starting
2: Always 3: Never
0: None; 1: Warning; 2: Block; 3: Safety Trip;
4: Safety Trip and Stop; 5: Trip; 6: Trip and
Stop; 7: Shutdown.
Time from detecting active to confirm
LCD displays detailed contents when the
input is active.
Normal generating output
0: Normally open;
1: Normally close
Common Alarm
0: Normally open;
1: Normally close
Energize to Stop