Smartgen HGM9510N User Manual page 62

Paralleled genset controller
Table of Contents

Advertisement

No.
Items
18.
Crank Disconnect
Disconnect
19.
Generator Freq
Disconnect Engine
20.
Speed
Disconnect
21.
Pressure
22.
ECU Fault Lamp
23.
ECU Stop Lamp
24.
ECU Warning Lamp
25.
ECU Protect Lamp
Generator Setting
1.
AC System
2.
Poles
3.
Rated Voltage
4.
Loading Voltage
5.
Gen Rated Freq.
6.
Loading Frequency
HGM9510N/HGM9530N Paralleled Genset Controller User Manual
Parameters
(0-6)
(0-200.0)%
(0-200.0)%
Oil
(0-1000)kPa
(0-7)
(0-7)
(0-7)
(0-7)
(0-3)
(2-64)
(30-30000)V
(0-200.0)%
(10.0-75.0)Hz
(0-200.0)%
Defaults
There are 3 conditions of disconnecting
starter with engine. Each condition can be
2
used alone and simultaneously to separate
the start motor and engine as soon as
possible.
Percentage
frequency; when generator frequency is
24.0
higher than the set value, starter will be
disconnected. See the below installation
instruction.
Percentage of the rated speed; when
generator speed is higher than the set
24.0
value, starter will be disconnected. See the
installation instruction.
When oil pressure is higher than the set
200
value, starter will be disconnected. See the
installation instruction.
1
0: None; 1: Warning; 2: Block; 3: Safety Trip;
7
4: Safety Trip and Stop; 5: Trip; 6: Trip and
1
Stop; 7: Shutdown.
1
0: 3P4W; 1: 3P3W;
0
2: 2P3W; 3: 1P2W.
Numbers of generator pole, used for
4
calculating engine speed when there is no
speed sensor.
To offer standards for detecting of gens'
over/under voltage and loading voltage. (It
is primary voltage when using voltage
230
transformer; it is line voltage when AC
system is 3P3W while it is phase voltage
when using other AC system).
Percentage of generator rated voltage; it is
detected when the controller prepares to
90.0
load; when the generating voltage is below
the load voltage. It won't enter normally
running period.
Offer
50.0
over/under/load frequency.
Percentage of generator rated frequency;
90
when generator frequency is under load
frequency, it won't enter normal running.
Description
of
the
generating
standards
for
Page 62 of 116
rated
detecting

Advertisement

Table of Contents
loading

This manual is also suitable for:

Hgm9530n

Table of Contents