Smartgen HGM9510N User Manual page 45

Paralleled genset controller
Table of Contents

Advertisement

No
Type
14
ECU Alarm
15
Temp. Sensor Open
16
Engine Temp High
17
Engine Temp Low
Oil Pressure Sensor
18
Open
19
Oil Pressure Low
Oil Pressure Sensor
20
Wrong
21
Fuel Level Sensor Open
22
Fuel Level Low
23
Flex. Sensor 1 Open
24
Flex. Sensor 1 High
25
Flex. Sensor 1 Low
HGM9510N/HGM9530N Paralleled Genset Controller User Manual
power (negative) is above the preset limit, it shall issue an alarm signal.
It is always detected.
When the controller receives the engine alarm signal from J1939, it
shall issue an alarm signal.
It is always detected.
When the controller detects the sensor circuit is open, it shall issue an
alarm signal.
It is always detected.
When this is enabled, and the controller detects the temp. is above the
preset limit, it shall issue an alarm signal.
It is detected after "safety on time" before "ETS solenoid hold".
When this is enabled, and the controller detects the temp. is below the
preset limit, it shall issue an alarm signal.
It is detected after "safety on time" before "ETS solenoid hold".
When the controller detects the sensor circuit is open, it shall issue an
alarm signal.
It is always detected.
When this is enabled, and the controller detects the pressure is below
the preset limit, it shall issue an alarm signal.
It is detected after "safety on time" before "ETS solenoid hold".
When voltage or current input is selected for the curve type of the
controller, and the controller detects input signal is abnormal, it shall
issue an alarm signal, and meanwhile the curve is transferred to
resistor type to prevent damaging the controller.
It is always detected.
When the controller detects the sensor circuit is open, it shall issue an
alarm signal.
It is always detected.
When this is enabled, and the controller detects the level is below the
preset limit, it shall issue an alarm signal.
It is always detected.
When the controller detects the sensor circuit is open, it shall issue an
alarm signal.
It is always detected.
When over high alarm is enabled, and the controller detects the sensor
value is above the preset upper limit, it shall issue an alarm signal.
It is detected after "safety on time" before "ETS solenoid hold" when the
sensor is selected as temperature sensor and pressure sensor;
It is always detected when the sensor is selected as fuel level sensor.
When over low alarm is enabled, and the controller detects the sensor
value is below the preset low limit, it shall issue an alarm signal.
It is detected after "safety on time" before "ETS solenoid hold" when the
sensor is selected as temperature sensor and pressure sensor;
Description
Page 45 of 116