Smartgen HGM9510N User Manual page 57

Paralleled genset controller
Table of Contents

Advertisement

No.
Functions
Genset C-phase voltage
49
input
50
Genset N-wire input
51
CT A-phase input
52
53
CT B-phase input
54
55
CT C-phase input
56
57
Earth CT input
58
59
Digi. input 8
60
Digi. input 9
61
Digi. input 10
62
Engine Temperature
63
Oil pressure
64
Fuel level
65
Flex. sensor 1
66
Flex. sensor 2
67
VOUT(+5V)
68
Sensor COM.
69
RS485(2) B(-)
70
RS485(2) A(+)
71
RS485(2) TR
72
MSC(2) CAN L
73
MSC(2) CAN H
74
MSC(2) TR
NOTE: USB ports on the controller rear panel are configurable parameter ports, and users can directly program the
controller on PC. ETHERNET port on the controller rear panel is parameter programming and monitoring port, and it can
be programmed and monitored on PC.
HGM9510N/HGM9530N Paralleled Genset Controller User Manual
Cable Size
Connect
2
1.0mm
recommended).
1.0mm
2
Connect to N-wire of genset.
2
1.5mm
Outside
1.5mm
2
transformer (rated 5A).
1.5mm
2
Outside
1.5mm
2
transformer (rated 5A).
1.5mm
2
Outside
2
transformer (rated 5A).
1.5mm
1.5mm
2
Outside
1.5mm
2
transformer (rated 5A).
1.0mm
2
Ground connected is active (B-).
1.0mm
2
Ground connected is active (B-).
2
1.0mm
Ground connected is active (B-).
1.0mm
2
Connect to temperature resistance sensor.
Connect to engine oil pressure sensor. Voltage type
1.0mm
2
(0-5V), current type (4mA-20mA) and resistance sensor
can be chosen.
2
1.0mm
Connect to fuel level resistance sensor.
Connect to temp./fuel level/pressure type sensor.
1.0mm
2
Voltage type (0-5V), current type (4-20mA) and
resistance sensor can be chosen.
1.0mm
2
Connect to temp./fuel level/pressure type sensor.
Provide +5V voltage for voltage type sensor, and current
1.0mm
2
is below 50mA.
Sensor public terminal, and B- is already connected in
/
the controller.
0.5mm
2
Impedance-120Ω shielding wire is recommended, and
0.5mm
2
the single-end shall be earth connected. Short connect
TR with A(+) and then connect to 120Ω terminal resistor.
/
2
0.5mm
Impedance-120Ω shielding wire is recommended, and
the single-end shall be earth connected. Short connect
2
0.5mm
TR with H and then connect to 120Ω terminal resistor.
/
(Not available for HGM9510N)
Remark
to
C-phase
of
genset
connect
to
secondary
connect
to
secondary
connect
to
secondary
connect
to
secondary
(2A
fuse
is
coil
of
current
coil
of
current
coil
of
current
coil
of
current
Page 57 of 116

Advertisement

Table of Contents
loading

This manual is also suitable for:

Hgm9530n

Table of Contents