8.3 DEFINED CONTENTS OF PROGRAMMABLE INPUT PORTS

Table 15 Definition of Digital Input Ports 1-10 (GND Connected (B-) is active)
No.
Type
0
Users Configured
1
Reserved
2
Alarm Mute
3
Reset Alarm
4
60Hz Active
5
Lamp Test
6
Panel Lock
7
Reserved
8
Idle Control Mode
9
Auto Stop Inhibit
10
Auto Start Inhibit
11
Scheduled Inhibit
12
Reserved
13
Gen Closed Aux
14
Gen Load Inhibit
15
Mains Closed Aux
16
Mains Load Inhibit
17
Auto Mode Lock
18
Auto Mode Inhibit
19
Controller Backlit
20
Controller Buzzer
21
Alarm Stop Inhibit
22
Instrument Mode
23
Reset Maintenance 1
24
Reset Maintenance 2
25
Reset Maintenance 3
26
High Temp. Shutdown
27
Low OP Shutdown
HGM9420N_HGM9420LT Genset Controller
HGM9420N_HGM9420LT GENSET CONTROLLER USER MANUAL
Users-defined alarm.
Active range:
Never: input inactive.
Always: input is active all the time.
From crank: detecting as soon as start.
From safety on: detecting after safety on run delay.
Can prohibit ‗Audible Alarm' output when input is active.
Can reset shutdown, trip and stop, trip, block and warning alarm when
input is active.
Use for CANBUS engine and it is 60Hz when input is active.
All LED indicators are illuminated when input is active.
All buttons on panel is inactive except navigation buttons and there is
in the right top corner in LCD when input is active.
Under voltage/frequency/speed protection is inactive.
In Auto mode, during generator normal running, when input is active,
prohibit generator shutdown automatically.
In Auto mode, prohibit generator start automatically when input is
active.
In Auto mode, prohibit scheduled start genset when input is active.
Connect generator loading switch's auxiliary point.
Prohibit genset switch on when input is active.
Connect mains loading switch's auxiliary point.
Prohibit mains switch close when input is active.
When input is active, controller enters into Auto mode.
When input is active, controller won't work under Auto mode. Auto key
on the panel and simulate auto key input do not work.
All shutdown alarms are prohibited except emergence stop.(Means
battle mode or override mode)
All outputs are prohibited in this mode.
Controller will set maintenance time and date as default when input is
active.
Connected sensor digital input.
Connected sensor digital input.
2019-12-10
Description
Version 1.0
Page 86 of 112