Smartgen HGM9510N User Manual page 76

Paralleled genset controller
Table of Contents

Advertisement

No.
Items
Active Output
10.
Curve
Reactive
Output
11.
Curve
GOV/AVR
1.
GOV SW1
2.
GOV SW2
3.
AVR SW1
4.
AVR SW2
Mains Setting
1.
AC System
2.
Rated Voltage
Mains
Rated
3.
Frequency
4.
Volt. Trans.(PT)
5.
Mains Split Action
6.
Mains Over Volt.
7.
Mains Under Volt.
8.
Mains Over Freq.
9.
Mains Under Freq.
10.
ROCOF
11.
Vector Shift
HGM9510N/HGM9530N Paralleled Genset Controller User Manual
Parameters
Defaults
(0-20.00)
0
(0-10.00)
2.00
(0-20.00)
0
(0-10.00)
2.0
(0-3)
0
(30-30000)V
230
(10.0-75.0)Hz
50.0
(0-1)
0
(0-1)
0
(0-1)
1
(0-200.0)%
110.0
(0-20.0)s
0.1
(0-1)
1
(0-200.0)%
90.0
(0-20.0)s
0.1
(0-1)
1
(0-200.0)%
101.0
(0-20.0)s
0.1
(0-1)
1
(0-200.0)%
99.0
(0-20.0)s
0.1
(0-1)
1
(0-1.00)Hz/s
0.20
(0-20.0)s
0.1
(0-1)
1
Description
mode is configured as Fixed Power.
Configure
gen
frequency-active
curve.
It is active when active power output mode
is configured as Frequency-Power.
Configure gen voltage-reactive power curve.
It is active when reactive power output
mode is configured as Voltage-Power.
Center voltage, default 0V.
Voltage range, default (-1.5~+1.5V).
Center voltage, default 0V.
Voltage range, default (-1.5~+1.5V).
0: 3P4W; 1: 3P3W;
2: 2P3W; 3: 1P2W.
Offer
standards
for
over/under voltage. It is primary voltage
when voltage transformer is used.
It is wire voltage when AC system is 3P3W
while it is phase voltage when other AC
system is used.
Offer standards for detecting over/under
frequency.
0: Disable ;
1: Enable
0: Trip and Stop; 1: Aux. Mains Failure.
Set value is percentage of mains rated
voltage.
Set value is mains rated frequency's
percentage.
Set value is frequency change rate of mains
(ROCOF).
Set value is phase angle's change rate of
power
detecting
mains'
Page 76 of 116