Smartgen HGM9510N User Manual page 72

Paralleled genset controller
Table of Contents

Advertisement

No.
Items
8.
Sets on Bus
Scheduling Sets
9.
Mode
Scheduling Start
10.
PCT
Scheduling Stop
11.
PCT
Scheduling Start
12.
Power
Scheduling Stop
13.
Power
Freq Coefficient
14.
Volt Coefficient
15.
Ground Relay Close
16.
Failure
Ground Relay Open
17.
Failure
Static Parallel
18.
Delay
Economy Fuel
19.
Economy Fuel (%)
20.
21.
Economy Swap(W)
22.
GOV Droop
23.
24.
HGM9510N/HGM9530N Paralleled Genset Controller User Manual
Parameters
Defaults
(1-32)
1
(0-1)
0
(0-100)%
80
(0-100)%
50
(0-6000)kW
200
(0-6000)kW
400
(0-200)%
10
(0-200)%
10
(0-7)
7
(0-7)
1
(0-600)s
60
(0-1)
0
(0-100)%
60
(0-6000)kW
200
(0-1)
0
(0-200.0)%
101.0
(0-200.0)%
100.0
Description
Balance
running
gensets
configured as the same priority.
Set the number of closed gensets on the
bus.
0: Gen Power (%); 1: Available Power.
Schedule the load value of other gensets
when start the genset on demand.
Schedule the load value of other genset
when start the genset on demand.
Schedule the available power value of other
genset when start the genset on demand.
Schedule the available power value of other
genset when start the genset on demand.
It is frequency feedback coefficient in
configuring active power distribution.
It is voltage feedback coefficient
configuring reactive power distribution.
0: None; 1: Warning; 2: Block; 3: Safety Trip;
4: Safety Trip and Stop; 5: Trip; 6: Trip and
Stop; 7: Shutdown.
0: None; 1: Warning; 2: Block; 3: Safety Trip;
4: Safety Trip and Stop; 5: Trip; 6: Trip and
Stop; 7: Shutdown.
If static paralleling is not completed during
"Static Parallel Delay", controller will initiate
alarm information.
0: Disable;
1: Enable
All gensets should be configured the same
economy fuel value.
It is the economy fuel percentage of genset.
Economy
fuel
consumption
exchange if difference value of the total
rated power of the exchange gensets and
the total power of the current loading
gensets is greater than the set exchange
power,
otherwise
performed.
0: Disable;
1: Enable
It is the percentage of no-load frequency
and rated frequency.
It is the percentage of full-load frequency
should
be
in
starts
no
exchange
is
Page 72 of 116