No.
Items
Load Control
1.
kW Control (Volt)
2.
kW Control (Relay)
kvar Control (Volt)
3.
4.
kvar Control (Relay)
Load
Load Minimum
1.
PCT
Load Mode
2.
Active Output Mode (0-1)
3.
Reactive
Output
4.
Mode
Output Active
5.
Power
Output
Reactive
6.
Power Option
Output
Reactive
7.
Power
Analogue Adjust
8.
(kW)
Analogue Adjust
9.
(kvar)
HGM9510N/HGM9530N Paralleled Genset Controller User Manual
Parameters
Defaults
(0-10.0)%
1.0
(0-500)%
20
(0-2000)%
20
(0-2000)%
0
(0.25-4.00)Hz/s
1.20
(0.05-1.60)s
0.20
(0-100)%
10
(0-10.0)%
1.0
(0-500)%
20
(0-2000)%
20
(0-2000)%
0
(0.25-4.00)Hz/s
1.20
(0.05-1.60)s
0.20
(0-100)%
10
(0-10.0)%
1.0
(0-100.0)%
1.0
(0-3)
0
0
(0-1)
0
(0-100.0)%
30.0
(0-1)
0
(0-100.0)%
8.0
(0-1)
0
(0-1)
0
Description
Dead area
Gain(P)
Stability(I)
Rate of change (D)
Response
Stability
Gain
Dead area
Gain(P)
Stability(I)
Rate of change (D)
Response
Stability
Gain
Dead area
It is the load percentage when the soft
unload is opened.
0: Gen; 1: Mains;
2: Takeover; 3: Load Control.
0: Fixed Power; 1: Frequency-Power.
It is active when Load mode is Gen control
mode.
0: Fixed Power; 1: Voltage-Power.
It is active when Load mode is Gen control
mode.
It is used to load control.
0: kvar Reactive Power Control;
1: PF Power Factor Control.
It is used to load control.
0: Disable; 1: Enable.
When it is enabled, flexible sensor 1 is used
as analog input.
It is active when active power output mode
is configured as Fixed Power.
0: Disable; 1: Enable.
When it is enabled, flexible sensor 2 is used
as analog input.
It is active when reactive power output
Page 75 of 116