Smartgen HGM9510N User Manual page 70

Paralleled genset controller
Table of Contents

Advertisement

No.
Items
2
Active Type
Digital Output Port 4
1
Contents Setting
2
Active Type
Digital Output Port 5
1
Contents Setting
2
Active Type
Digital Output Port 6
1
Contents Setting
2
Active Type
Digital Output Port 7
1
Contents Setting
2
Active Type
Digital Output Port 8
1
Contents Setting
2
Active Type
Scheduled Run
1
Scheduled Run
Scheduled Not Run
1
Scheduled Not Run
Maintenance Setting
1
Maintenance
Alternative Configuration
1
Alt. Config. 1
2
Alt. Config. 2
3
Alt. Config. 3
Sync Setting
Auto Sync
1
GOV Output Type
2
GOV Reverse
3
GOV Action
HGM9510N/HGM9530N Paralleled Genset Controller User Manual
Parameters
Defaults
(0-1)
0
(0-299)
35
(0-1)
0
(0-299)
30
(0-1)
0
(0-299)
29
(0-1)
0
(0-299)
0
(0-1)
0
(0-299)
0
(0-1)
0
(0-1)
0
(0-1)
0
(0-1)
0
(0-1)
0
(0-1)
0
(0-1)
0
(0-1)
1
(0-1)
0
(0-2)
1
Description
0: Normally open;
1: Normally close
Idle Control
0: Normally open;
1: Normally close
Open Gen Output
0: Normally open;
1: Normally close
Close Gen Output
0: Normally open;
1: Normally close
Not Used
0: Normally open;
1: Normally close
Not Used
0: Normally open;
1: Normally close
0: Disable; 1: Enable
Circular setting (monthly, weekly, daily),
start time setting, continuous time setting
and loading setting are available.
0: Disable; 1: Enable
Circular setting (monthly, weekly, daily),
non-start time setting and continuous time
setting are available.
0: Disable; 1: Enable
Maintenance time, alarm action can be set.
0: Disable; 1: Enable
Power supply system, rated voltage, rated
frequency, rated speed, rated current, rated
active power, rated reactive power, GOV
SW1, AVR SW1 can be set.
0: Disable;
1: Enable
0: Disable;
1: Enable
0: Internal Relays; 1: Internal Analogue
0: Disable;
1: Enable
0: None; 1: Adjust to Rated; 2: Adjust to
Page 70 of 116

Advertisement

Table of Contents
loading

This manual is also suitable for:

Hgm9530n

Table of Contents