Smartgen HGM9510N User Manual page 79

Paralleled genset controller
Table of Contents

Advertisement

No.
31
Reserved
32
Reserved
33
Crank Relay
34
Fuel Relay
35
Idle Control
36
Speed Raise Output
37
Speed Drop Output
38
Energize to Stop
39
Speed Drop Pulse
40
ECU Stop
41
ECU Power Supply
42
Speed Raise Pulse
43
Crank Success
44
Gen OK
45
Gen Load Available
46
Reserved
47
Synchronizing
48
Common Alarm
49
Common Trip and Stop
50
Common Shutdown
51
Common Trip
52
Common Warn
53
Common Block
54
Battery Over Voltage
55
Battery Under Voltage
56
Charge Alternator Failure
57
Common Safety Stop
58
Common Safety Trip
59
Reserved
60
ECU Warning
61
ECU Shutdown
62
ECU Comm. Failure
63
PWM Voltage Raise
HGM9510N/HGM9530N Paralleled Genset Controller User Manual
Type
Act when genset is starting and disconnect when stop is
completed.
When gas timer is enabled, fuel relay output is used to control
gas valve.
It is used for genset with idling control. Close before starting
and open in warming up delay; Close during stopping idle
mode and open when stop is completed.
Act during warming up time.
Act between the period "stop idle" and "failed to stop".
It is used for engines with ETS electromagnet. Close when
stop idle is over and open when pre-set "ETS delay" is over.
Act for 0.1s when controller enters "stop idle", used for control
parts of ECU dropping to idle speed.
Used for ECU engine and control its stop.
Used for ECU engine to control its power.
Act for 0.1s when controller enters warming up delay; used for
control parts of ECU raising to normal speed.
Close when a successful start signal is detected.
Act when generator is normally running.
Act between normal running and high-speed cooling.
Act when controller is synchronizing.
Act when genset common warning, common shutdown,
common trip alarms occur.
Act when common trip and stop alarm occurs.
Act when common shutdown alarm occurs.
Act when common trip alarm occurs.
Act when common warning alarm occurs.
Act when battery's over voltage warning alarm occurs.
Act when battery's low voltage warning alarm occurs.
Act when charging failure warning alarm occurs.
Indicates ECU sends a warning signal.
Indicates ECU sends a shutdown signal.
Indicates controller cannot communicating with ECU.
When output type of AVR is set as "Relay output", controller
Description
Page 79 of 116

Advertisement

Table of Contents
loading

This manual is also suitable for:

Hgm9530n

Table of Contents